Table of Contents Table of Contents
Previous Page  262 / 338 Next Page
Information
Show Menu
Previous Page 262 / 338 Next Page
Page Background

D-28

Additional information

Electrical characteristics

Masterpact NW08 à NW16

Drawout

Vertical busbars on the left or right

Linergy LGY, BS busbars

Connections drawings supplied by

Schneider Electric

Dd383669.eps

1

Connection.

2

Horizontal link.

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making the connections to busbars for a

vertical, drawout Masterpact NW08/NW16, front or rear connection, taking into

account the ambient temperature around the switchboard and the IP value.

Connection

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

(1)

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08

Size per phase

1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10

Size per phase

1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

NW12

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200

NW16

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330

(1)

In the case of a door mounted at the rear of cubicle, add 10 °C.

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Horizontal link

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08

Size per phase

1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10

Size per phase

1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

NW12

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1230 1250 1200 1230 1160 1200

NW16

Size per phase

2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1560 1480 1520 1430 1480 1380 1430 1330 1380 1280 1330

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designing connections between

a device and busbars

Drawout Masterpact NW08 to NW16