Table of Contents Table of Contents
Previous Page  265 / 338 Next Page
Information
Show Menu
Previous Page 265 / 338 Next Page
Page Background

D-31

Additional information

Electrical characteristics

Masterpact NW08 à NW32

Drawout

Dedicated cubicle

Linergy LGYE, BS busbars

Connections drawings supplied by

Schneider Electric

DD385490.eps

Connection

Flat bars, 10 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

1000

NW12 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1250

1250

1250

1210

1250

1180

1210

1140

1180

1100

1140

NW16 Size per phase 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10 1b 80 x 10

bb

I (A)

1560

1480

1520

1430

1480

1380

1430

1330

1380

1280

1330

NW20 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10

bb

I (A)

2000

2000

2000

1950

2000

1900

1950

1830

1900

1760

1830

NW25 Size per phase 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10 2b 80 x 10

bb

I (A)

2470

2280

2410

2210

2350

2140

2280

2070

2210

2000

2140

NW32 Size per phase 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10 3b 80 x 10

bb

I (A)

2960

2730

2890

2630

2820

2530

2730

2450

2630

2370

2530

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

contact Schneider Electric for 4000 A dedicated cubicle

Designing connections between

a device and busbars

Dedicated cubicle

Drawout Masterpact NW08 to NW32