D-26

Additional information

Electrical characteristics

Masterpact NW08 à NW16

Fixed

Vertical busbars on the left or right

Linergy LGY, BS busbars

Connections drawings supplied by

Schneider Electric

Dd383667.eps

1

Liaison

2

Horizontal link.

Using the data below, it is possible to determine the size of the copper bars and the

maximum permissible currents when making the connections to busbars for a

vertical, fixed Masterpact NW08/NW16, front or rear connection, taking into account

the ambient temperature around the switchboard and the IP value.

Connection

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

(1)

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

NW12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250

NW16 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470

(1)

In the case of a door mounted at the rear of cubicle, add 10 °C.

Horizontal link

Flat bars, 5 mm thick

Device

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

NW08 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

800

800

800

800

800

800

800

800

800

800

800

NW10 Size per phase 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5 1b 80 x 5

bb

I (A)

1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

NW12 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1250 1250 1250 1250 1250 1250 1250 1250 1250 1250 1250

NW16 Size per phase 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5 2b 80 x 5

bb

I (A)

1600 1600 1600 1570 1600 1520 1570 1470 1520 1420 1470

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Note:

the values indicated above have been validated for Prisma P switchboards.

Designing connections between

a device and busbars

Fixed Masterpact NW08 to NW16