Table of Contents Table of Contents
Previous Page  253 / 338 Next Page
Information
Show Menu
Previous Page 253 / 338 Next Page
Page Background

D-19

Additional information

Designing vertical busbars

Linergy LGY

Electrical characteristics

Permissible current and selection of Linergy LGY busbars

The goal is to optimise busbar size according to the installation and operating

criteria.

Up to 3200 A

Linergy LGY section

Type of bars

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

Linergy LGY 630

750

680

710

630

680

590

630

550

590

530

550

bb

Linergy LGY 800

920

840

880

800

840

760

800

720

760

680

720

bb

Linergy LGY 1000

1140 1040 1090 990

1040 950

990

900

950

850

900

bb

Linergy LGY 1250

1410 1290 1350 1230 1290 1170 1230 1100 1170 1050 1100

bb

Linergy LGY 1600

1800 1650 1720 1580 1650 1480 1580 1390 1480 1320 1390

bb

Linergy LGY 2000 (2 x 1000)

2200 2000 2100 1900 2000 1820 1900 1720 1820 1620 1720

bb

Linergy LGY 2500 (2 x 1250)

2740 2500 2620 2380 2500 2260 2380 2120 2260 2020 2120

bb

Linergy LGY 3200 (2 x 1600)

3480 3200 3340 3060 3200 2920 3060 2780 2920 2640 2780

bb

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

Example:

A Linergy LGY channelled bar can be used for a 1650 A current with an IP

y

31 and

an ambient temperature around the switchboard of 35 °C.

DD381233.eps

DD381234.eps

DD381235.eps

DD385507.eps

Section 630 A.

Cat. No. 04502.

Section 800 A.

Cat. No. 04503.

Section 1000 A.

Cat. No. 04504.

Section 1250 A.

Cat. No. 04505.

DD385508.eps

Section 1600 A.

Cat. No. 04506.

Note:

the values indicated above have been validated for Prisma P switchboards.