Additional information

Designing Prisma P

power circuits

Presentation and approach

Electrical characteristics

Prisma P takes into account the installation and

connection conditions of Schneider Electric devices.

The entire installation complies with standard

IEC 60439-1. The result is a type tested switchboard.

In the following pages you will find a number of examples, validated for Prisma P

switchboards, intended to assist in determining the busbars as well as the upstream

and downstream connections for the installation.

The examples assume that the devices have already been selected.

A complete process involves a number of steps before making final choices

(transformer, conductors, protection, etc.).

Schneider Electric offers a number of tools to assist in designing a complete

installation (technical guides, software).

PD390311_SE.eps

Busbar sizing

The factors that must be taken into account in determining the size of busbars

include:

bb

the diversity factor.

Not all the loads supplied by a set of busbars are used at full rated load or at the

same time. The diversity factor is the means to determine the maximum load current

used to size the busbars.

Standard IEC 61439-1 and 2 §4.7 specifies the table below.

Number of circuits

Diversity factor

2 and 3

0,9

4 and 5

0,8

6 and 9

0,7

10 and more

0,6

b

the degree of protection IP.

b

the ambient temperature around the switchboard.