Table of Contents Table of Contents
Previous Page  254 / 338 Next Page
Information
Show Menu
Previous Page 254 / 338 Next Page
Page Background

D-20

Additional information

Designing vertical busbars

Linergy LGYE

Permissible current and selection of Linergy LGYE busbars

Up to 4000 A

Linergy LGYE section

Type of bars

Permissible current (A)

Ambient temperature around the switchboard

25 °C

30 °C

35 °C

40 °C

45 °C

50 °C

Size per phase

IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31 IP

y

31 IP > 31

Linergy LGYE 630

680

580

650

550

630

530

590

500

550

470

520

bb

Linergy LGYE 800

860

740

830

710

800

680

750

630

700

600

660

bb

Linergy LGYE 1000

1080 920

1040 884

1000 850

940

790

880

750

830

bb

Linergy LGYE 1250

1350 1150 1300 1100 1250 1050 1170 1000 1100 930

1020

bb

Linergy LGYE 1600

1730 1580 1690 1530 1650 1480 1550 1380 1450 1300 1350

bb

Linergy LGYE 2000

2200 1810 2100 1730 2000 1650 1900 1560 1810 1480 1720

bb

Linergy LGYE 2500

2640 2230 2540 2160 2440 2100 2310 2000 2240 1930 2120

bb

Linergy LGYE 3200

3400 3020 3300 2900 3200 2800 3040 2660 2890 2520 2750

bb

Linergy LGYE 4000

3800 3510 3710 3430 3620 3350 3450 3180 3280 3020 3120

bb

bb

Connection impossible due to the operating-temperature limits of the devices installed in the switchboard.

DD384545.eps

DD384546.eps

DD384547.eps

DD384548.eps

DD384549.eps

Section 630 A.

Cat. No. 04560.

Section 800 A.

Cat. No. 04561.

Section 1000 A.

Cat. No. 04562.

Section 1250 A.

Cat. No. 04563.

Section 1600 A.

Cat. No. 04564.

DD384550.eps

DD384551.eps

DD384552.eps

DD384553.eps

Section 2000 A.

Cat. No. 04565.

Section 2500 A.

Cat. No. 04566.

Section 3200 A.

Cat. No. 04567.

Section 4000 A.

Cat. No. 04568.

Electrical characteristics