Background Image
Table of Contents Table of Contents
Previous Page  130 / 439 Next Page
Information
Show Menu
Previous Page 130 / 439 Next Page
Page Background

5/126

Contactors

Basic devices up to 200 A, 4 pole

2010

CA08103002Z-EN

www.eaton.com

Basicdevicesup to 200A, 4pole

DILMP20

DILMP32

DILMP63

DILMP125

DILMP45

DILMP80

DILMP160

DILMP200

DC voltage

Rated operational current I

e

open

DC-1 operation

60

V

I

e

A

22

32

45

63

80

125

160

200

110

V

I

e

A

22

32

45

63

80

125

160

200

220

V

I

e

A

6

32

45

63

80

125

160

200

440

V

I

e

A

1.3

3

3

5

5

10

10

10

DC-3 operation

60

V

I

e

A

20

32

45

63

80

125

160

200

110

V

I

e

A

20

32

45

63

80

125

160

200

220

V

I

e

A

1.5

32

45

63

80

125

160

200

440

V

I

e

A

0.2

6

6

8

8

9

9

9

DC-5 operation

60

V

I

e

A

20

32

45

63

80

125

160

200

110

V

I

e

A

20

25

32

50

80

125

160

200

220

V

I

e

A

1.5

15

22

38

70

100

125

150

440

V

I

e

A

0.2

4

4

8

8

8

8

8

Current heat loss (3 pole)

Current heat loss at I

th

W 4.7

8.2

12

16

23

29

46

60

Impedance per pole

mΩ

2.5

2

1.5

1

0.7

0.6

0.6

0.5

Magnet systems

Voltage tolerance

AC operated 50 Hz

Pick-up

x U

c

0.8 - 1.1

0.8 - 1.1

0.8 - 1.1

0.8 - 1.1

AC operated 50/60 Hz

x U

c

0.8 - 1.1

0.85 - 1.1

0.85 - 1.1

0.8 - 1.1

AC operated

Drop-out

x U

c

0.4 - 0.6

0.4 - 0.6

0.4 - 0.6

0.4 - 0.6

DC operated

1)

Pick-up

x U

c

0.8 - 1.1

0.7 - 1.2

0.7 - 1.2

0.7 - 1.2

DC operated

1)

Drop-out

x U

c

0.2 - 0.6

0.2 - 0.6

0.2 - 0.6

0.2 - 0.6

Power consumption of the coil in a cold state and 1.0 x U

c

AC operated 50/60 Hz

Pick-up

VA

24

50

150

180

AC operated 50/60 Hz

Pick-up

W 19

40

95

150

AC operated 50/60 Hz

Sealing

VA

4

8

16

3.1

AC operated 50/60 Hz

Sealing

W 1.2

2.4

4

2.1

DC operated

1)

Pick-up

W 4.5

12

24

149

DC operated

1)

Sealing

W 4.5

0.5

0.5

2.1

Duty factor

%

DF

100

100

100

100

Changeover times at 100 % U

c

(

recommended values)

Main contacts

AC operated

Closing delay

ms

15…21

16…22

12…18

28…33

Opening delay

ms

9…18

8…14

8…13

35…41

DC operated

1)

Closing delay

ms

31

47

54

35

Opening delay

ms

12

30

24

30

Arcing time

ms

10

10

10

15

Permissible residual current when A1 - A2 are

actuated from the electronic system (with 0 signal)

mA

≦ 1

≦ 1

≦ 1

≦ 1

Notes

1)

At least double-pulse bridge rectifier

DILMP20 ... DILMP200