5/130
Contactors
Contactors up to 150 A with electronic actuation
2010
CA08103002Z-EN
www.eaton.comContactorsup to 150Awithelectronicactuation
DILMF8
DILMF11
DILMF14
DILMF17
General
Mounting position
AC voltage
AC-3 operation
Rated operational current AC -3 open,
50 – 60
Hz, 3 pole
220/230
V
I
e
A
7
9
12
18
240
V
I
e
A
7
9
12
18
380/400
V
I
e
A
7
9
12
18
415
V
I
e
A
7
9
12
18
440
V
I
e
A
7
9
12
18
500
V
I
e
A
5
7
10
18
660/690
V
I
e
A
4
5
7
12
Rated operational power
220/230
V
P
kW 2.2
2.5
3.5
5
240
V
P
kW 2.2
3
4
5.5
380/400
V
P
kW 3
4
5.5
7.5
415
V
P
kW 4
5.5
7
10
440
V
P
kW 4.5
5.5
7.5
10.5
500
V
P
kW 3.5
4.5
7
12
660/690
V
P
kW 3.5
4.5
6.5
11
AC-4 operation
Rated operational current AC-4 open,
50 - 60
Hz, 3 pole
220/230
V
I
e
A
5
6
7
10
240
V
I
e
A
5
6
7
10
380/400
V
I
e
A
5
6
7
10
415
V
I
e
A
5
6
7
10
440
V
I
e
A
5
6
7
10
500
V
I
e
A
4.5
5
6
10
660/690
V
I
e
A
4
4.5
5
8
Rated operational power
220/230
V
P
kW 1
1.5
2
2.5
240
V
P
kW 1.5
1.6
2.2
3
380/400
V
P
kW 2.2
2.5
3
4.5
415
V
P
kW 2.3
2.8
3.4
5
440
V
P
kW 2.4
3
3.6
5.5
500
V
P
kW 2.5
2.8
3.5
6
660/690
V
P
kW 2.9
3.6
4.4
6.5
Current heat loss (3 pole)
Current heat loss at I
th
W 2.4
2.4
2.4
7.3
Current heat loss at I
e
to AC-3/400 V
W 0.3
0.6
1
1.9
Magnet systems
Voltage tolerance
AC operated
Pick-up x U
c
0.8 - 1.15
0.8 - 1.15
0.8 - 1.15
0.8 - 1.15
AC operated
Drop-out
x U
c
0.2 - 0.5
0.2 - 0.5
0.2 - 0.5
0.2 - 0.5
Power consumption of
the coil in a cold state
and 1.0 x U
c
Electronic actuation
Pick-up VA 14
14
14
14
Electronic actuation
Sealing VA 0.7
0.7
0.7
0.7
Electronic actuation
Sealing W 0.7
0.7
0.7
0.7
Duty factor
%
DF 100
100
100
100
Switching times
Closing delay
ms
40
40
40
40
Opening delay
ms
45
45
45
45
suitable according to
SEMI F47
SEMI F47
SEMI F47
SEMI F47
Electromagnetic compatibility (EMC)
Emitted interference
To EN 60947-1
Interference immunity
To EN 60947-1
Further technical data
As per contactor
DIL
M7
M9
M12
M17
Terminal type
As per contactor
DIL
M17
M17
M17
M17
180
°
90
°
90
°
30
˚
30
˚
DILMF