14/8
Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
14
Combined Type 1 and 2 tested protector (to BS EN 61643) for a Photovoltaic
PV solar panel system that is on a building where a structural Lightning
Protection System (LPS) is employed, for equipotential bonding. For use at
boundaries up to LPZ
0
to protect against flashover (on the DC side of
the DC-AC inverter) through to LPZ 2 to protect the PV system from damage.
Specific systems protection
ESP PV Series
IMPORTANT:
The primary purpose of lightning current or equipotential bonding mains Type 1 Surge Protective Devices (SPDs) is to prevent dangerous sparking caused by flashover to protect against
the loss of human life. In order to protect electronic equipment and ensure the continual operation of systems, transient overvoltage mains Type 2 and 3 SPDs such as the ESP M1 or ESP D1 Series
are further required, typically installed at downstream sub-distribution boards feeding sensitive equipment. IEC/BS EN 62305 refers to the correct application of mains Type 1, 2 and 3 SPDs as a
coordinated set. For further information, please refer to the Furse Guide to BS EN 62305 Protection against Lightning.
Installation
Protector should be installed in the main distribution board
with connecting leads of minimal length. The protector should
be fused and is suitable for attachment to a 35 mm top hat
DIN rail. Install in parallel to the DC supply of the DC-AC
inverter via fuses.
Accessories
WBX D4
Weatherproof enclosure
Full product range order codes can be found on pages 17/8-17/9
From PV Panel
+
-
+
-
+
-
ToDC
inputof
inverter
Features & benefits
–– Enhanced protection (to IEC/BS EN 62305) offering low
let-through voltage further minimizing the risk of flashover
creating dangerous sparking or electric shock
–– Repeated protection in lightning intense environments
–– The varistor based design eliminates the high follow current
(If) associated with spark gap based surge protection
–– Compact, space saving design
–– Indicator shows when the protector requires replacement
–– Remote signal contact can indicate the protector’s
status through interfacing with a building
management system
Application
Use on the DC side of the DC-AC inverter for protection
against partial direct or indirect lightning strikes. ESP Type
1 AC mains protectors (e.g. ESP 415/III/TNS) are further
required at the AC side of the DC-AC inverter.