Total Solution to Earthing & Lightning Protection |
9AKK106354A3360
14/9
14
ESP PV Series - Technical specification
Electrical specification
ESP DC550/12.5/PV
ESP DC1000/12.5/PV
ABB order code
7TCA085460R0147
7TCA085460R0146
Maximum DC voltage (RMS/DC)
550 V
1000 V
Short circuit withstand capability
25 kA/50 Hz
Leakage current (to earth)
< 2.5 mA
Volt free contact:
Screw terminal
– current rating
0.5 A
– nominal voltage (RMS)
250 V
Back up fuse
Fuses specifically designed for use on PV systems are recommended. Determine the most appropriate back up
fuse from assessment of the nominal current of the PV module, and the open circuit voltage of the PV array:
– Multiply the nominal current of the photovoltaic module by a factor of 1.4 and select the closest, higher
value fuse to the calculated figure.
– Multiply the open circuit voltage of the PV array by a factor of 1.2 and ensure that the selected fuse has a
higher voltage withstand than the calculated figure.
Transient specification
ESP DC550/12.5/PV
ESP DC1000/12.5/PV
Type 1 (BS EN/EN), Class I (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
Let-through voltage
U
p at In
(1)
< 2.0 kV
< 2.6 kV
Impulse discharge current 10/350 μs
I
imp (per mode)
(2)
12.5 kA
Let-through voltage
U
p at
I
imp
(1)
< 1.7 kV
< 2.4 kV
Type 2 (BS EN/EN), Class II (IEC)
Nominal discharge current 8/20 μs (per mode)
I
n
20 kA
Let-through voltage Up at
I
n
(1)
< 2.0 kV
< 2.6 kV
Maximum discharge current
I
max (per mode)
(2)
40 kA
Mechanical specification
ESP DC550/12.5/PV
ESP DC1000/12.5/PV
Temperature range
-40 to +80 ºC
Connection type
Screw terminal
Conductor size (stranded)
25 mm
2
Earth connection
Screw terminal
Volt free contact
Connect via screw terminal with conductor up to 1.5 mm
2
(stranded)
Degree of protection (IEC 60529)
IP20
Case Material
FR Polymer UL-94 V-0
Mounting
Indoor, 35 mm top hat DIN rail
Weight: – Unit
0.38 kg
0.59 kg
– Packaged
0.48 kg
0.69 kg
Dimensions to DIN 43880 - HxDxW:
(3)
90 mm x 68 mm x 72 mm (4TE)
(1)
The maximum transient voltage let-through of the protector
throughout the test, per mode
(2)
The electrical system, external to the unit, may constrain the
actual current rating achieved in a particular installation
(3)
The remote signal contact (removable) adds 10 mm to height
72 mm
4 TE
90 mm
45 mm
51 mm
Standard
depth 68 mm
Specific systems protection
ESP PV Series