Combined Type 1 and 2 tested protector (to BS EN 61643) for use on the
main distribution board within wind turbines, for equipotential bonding.
For use at boundaries up to LPZ
0
to protect against flashover (typically
the main distribution board location) through to LPZ 2 to protect electrical
equipment from damage.
Specific systems protection
ESP WT Series
IMPORTANT:
The primary purpose of lightning current or equipotential bonding mains Type 1 Surge Protective Devices (SPDs) is to prevent dangerous sparking caused by flashover to protect against
the loss of human life. In order to protect electronic equipment and ensure the continual operation of systems, transient overvoltage mains Type 2 and 3 SPDs such as the ESP M1 Series or ESP D1
Series are further required, typically installed at downstream subdistribution boards feeding sensitive equipment. IEC/BS EN 62305 refers to the correct application of mains Type 1, 2 and 3 SPDs as
a coordinated set. For further information, please refer to the Furse Guide to BS EN 62305 Protection against Lightning.
Installation
Protector should be installed in the main distribution board
with connecting leads of minimal length. The protector should
be fused and is suitable for attachment to a 35 mm top
hat DIN rail. The diagrams below illustrate how to wire
the appropriate ESP protector according to your chosen
electrical system.
Accessories
Connecting and earthing bars
ESP CE7
Use with 3 of ESP 690/12.5/WT for
TN-C supplies
ESP CE9
Use with 3 of ESP 690/25/WT for
TN-C supplies
ESP CE10
Use with 4 of ESP 690/12.5/WT for
TN-S supplies
ESP CE13
Use with 4 of ESP 690/25/WT for
TN-S supplies
For suitable enclosures for the ESP WT series,
please contact us.
Full product range order codes can be
found on pages 17/8-17/9
TN-S earthing system (ESP WT x 4 with
ESP CE10 or ESP CE13 earthing bars
TN-C earthing system (ESP WT x 3) with
ESP CE7 or ESP CE9 earthing bars
Features & benefits
–– Enhanced protection (to IEC/BS EN 62305) offering low
let-through voltage further minimizing the risk of flashover
creating dangerous sparking or electric shock
–– Repeated protection in lightning intense environments
–– The varistor based design eliminates the high follow current
(
I
f
) associated with spark gap based surge protection
–– Indicator shows when the protector requires replacement
–– Remote signal contact can indicate the protector’s
status through interfacing with a building
management system
Application
Use on 690 V three phase mains power supplies and power
distribution boards for protection against partial direct and
indirect lightning strikes. The services (typically 3 phase
400 V mains, UPS, data, signal and telecom lines) to the
cabinet within the wind turbine nacelle will require
additional protection.
–– For a 3 phase TN-S supply, install 4 ESP WT units together
with ESP CE10 or ESP CE13 connecting and earthing bar
(see installation)
–– For a 3 phase TN-C supply, install 3 ESP WT units together
with ESP CE7 or ESP CE9 connecting and earthing bar
(see installation)