ESP SSI Series - Technical specification

Electrical specification

ESP SSI/M

ESP SSI/B

ABB order code

7TCA085400R0168 7TCA085400R0166

Maximum signal voltage

(1)

7 V

Maximum common mode stand-off voltage

90 Vrms

Current rating

100 mA

10 A, 250 V

In-line resistance (per line, ±10%)

4.5 Ω

Leakage: – (Line to line impedance)

> 1 MΩ

– (Line to earth impedance)

> 10 kΩ

Differential bandwidth (50 Ω system)

10 MHz

ESP SSI/B:

This is a modified 11 pin ‘relay type’ socket containing a 100 Ω ±5%

wire-wound 2.5 W resistor connected between terminals 8 and 9.

Internal links between terminals 2 & 3, 9 & 10, and 1 & 11.

Transient specification

ESP SSI/M

ESP SSI/B

Transverse (Differential) ‘let-through’

voltage

(2)

U

p

15 V

Common mode ‘let-through’ voltage

(3)

U

p

250 V

Mechanical specification

ESP SSI/M

ESP SSI/B

Temperature range

-40 to +80 ºC

Connection type

Screw terminal

Fixing connection:

2 x M4 fixing holes

– Flat mount

with 33 mm centres

– Top Hat Din rail mount (ESP SSI/B)

An integral clip

– G Din rail mount (ESP SSI/B/G)

2 x mounting clips

with screws

Case material

FR Polymer UL-94 V-0

Weight: – Unit

0.065 kg

0.075 kg

– Packaged (per 50)

3.25 kg

3.9 kg

Dimensions

See diagram below

(1)

Maximum signal voltage (DC or AC peak) measured at 200 μA

(2)

‘Let-through’ voltage is the maximum transient voltage

‘let-through’ to the equipment to be protected.

C2 test (to BS EN/EN/IEC 61643-21) 2 kV 1.2/50 μs.

1 kA 8/20 μs. ‘Let-through’ voltage (±10%)

(3)

‘Let-through’ voltage is the maximum transient voltage

‘let-through’ to the equipment to be protected.

C2 test (to BS EN/EN/IEC 61643-21) 4 kV 1.2/50 μs.

2 kA 8/20 μs. ‘Let-through’ voltage (±20%)

(4)

Minimum permissible load is 5 V DC, 10 mA to ensure reliable

contact operation

(5)

The maximum transient voltage let-through of the protector

throughout the test (±10%), per mode

(6)

The electrical system, external to the unit, may constrain the

actual current rating achieved in a particular installation

(7)

Combination wave test within IEEE C62.41-2002 Location Cats

C1 & B3, SS CP 33:1996 App. F, AS 1768-1991 App. B, Cat B,

UL1449 mains wire-in

Electrical specification

ESP SSI/120AC

ESP SSI/140AC

ABB order code

7TCA085460R0059 7TCA085460R0060

Nominal voltage - Phase - Neutral

U

o (RMS)

120 V

140 V

Maximum working voltage - Phase -

Neutral

U

c (RMS)

150 V

165 V

Working voltage (RMS)

90-150 V

90-165 V

Frequency range

47-63 Hz

Current rating (supply) -

see installation instructions

100 A

Leakage current (to earth)

< 60 μA

Indicator circuit current

< 10 mA

Volt free contact:

(4)

Screw terminal

– Current rating

> 1 MΩ

– Nominal voltage (RMS)

> 10 kΩ

Transient specification

ESP SSI/120AC

ESP SSI/140AC

Let-through voltage (all conductors) Type 2 (BS EN/EN), Class II (IEC)

Nominal discharge current 8/20 μs

(per mode)

I

n

5 kA

Let-through voltage Up at

I

n

(5)

460 V

540 V

Maximum discharge current

I

max

(per mode)

(6)

20 kA

Type 3 (BS EN/EN), Class III (IEC)

Let-through voltage at

U

oc

of 6 kV 1.2/50 μs

and

I

sc

of 3 kA 8/20 μs (per mode)

(7)

400 V

500 V

Mechanical specification

ESP SSI/120AC

ESP SSI/140AC

Temperature range

-40 to +80 ºC

Connection type

Screw terminal

Conductor size (stranded)

16 mm

2

Earth connection

Screw terminal

Volt free contact

Connect via screw terminal with

conductor up to 2.5 mm

2

(stranded)

Case material

Steel

Weight: – Unit

0.5 kg

– Packaged

0.6 kg

Dimensions

See diagram below

50 mm

40 mm

43 mm

ESP SSI

120/AC

or

ESP SSI

140/AC

ESP SSI/M

50 mm

176 mm

165 mm

56 mm

Depth: 44 mm

Depth: 70 mm

M5 clearance

Depth: 69 mm

35 mm

ESP SSI/B

50 mm

40 m

43 mm

ESP SSI

120/AC

or

ESP SSI

140/AC

ESP SSI/M

50 mm

176 mm

165 mm

56 mm

Depth: 44 mm

Depth: 70 mm

M5 clearance

Depth: 69 mm

35 mm

ESP SSI/B

Specific systems protection

ESP SSI Series