Table of Contents Table of Contents
Previous Page  286 / 336 Next Page
Information
Show Menu
Previous Page 286 / 336 Next Page
Page Background

14/14

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

14

Combined Category D, C, B tested protector (to BS EN 61643) suitable for

coaxial CCTV cables with BNC connectors (ESP CCTV/B) or twisted pair CCTV

lines (ESP CCTV/T) on systems with either an earthed or an isolated screen.

Not suitable for use on broadcast, satellite or cable TV systems. For use at

boundaries up to LPZ

0

to protect against flashover (typically the service

entrance location) through to LPZ 3 to protect sensitive electronic equipment.

Specific systems protection

ESP CCTV Series

Installation

Connect in series with the CCTV cable in a convenient place

close to the equipment being protected. For outdoor CCTV

cameras, protectors should be mounted in the junction box, or

in a separate enclosure, close to the camera. Protect central

control and monitoring equipment inside the building by

installing protectors on all incoming or outgoing lines, either:

a) near where they enter or leave the building, or

b) close to the equipment being protected (or actually within

its control panel).

Accessories

When CCTV protectors are installed in groups, or alongside

protectors for signal and mains power lines, these can be

mounted and earthed simultaneously on a CME kit. A CME

4 will accommodate the video, telemetry and power

protectors to a camera. If protectors cannot be incorporated

within an existing panel or enclosure, WBX enclosures are

available for up to 4, 8, 16 or 32 protectors and their

associated CME kit. The WBX 4/GS is a secure IP66

enclosure suitable for a CME 4 and associated protectors.

Series connection for ESP CCTV/B

DIRTY

CLEAN

From line

Earth

To equipment

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning

currents as well as allowing continual operation of

protected equipment

–– Repeated protection in lightning intense environments

–– 100 MHz bandwidth prevents the degradation of high

frequency signals

–– Low in-line resistance to minimize unnecessary reductions

in signal strength and maximizes signalling distance

–– Very low reflection coefficient/VSWR ensure that the

protector doesn’t disrupt system operations

–– Suitable for either earthed or isolated screen systems

–– Sturdy, conductive ABS housing for 2 way shielding -

preventing emissions & providing signals with immunity

from external interference

–– Convenient holes for flat mounting on base or side

–– Built-in DIN rail foot for easy installation on a top hat DIN rail

–– ESP CCTV/T has colour coded terminals for a quick and

easy installation check - grey for the dirty (line) end and

green for the clean end

–– Substantial earth stud to enable effective earthing

–– Integral earthing plate for enhanced connection to earth

via CME kit

–– ESP CCTV/B has Network Rail Approval PA05/02510.

NRS PADS reference 086/023410

Application

Use these protectors on the video cable to outdoor CCTV

cameras and central control and monitoring equipment.

NOTE:

Camera telemetry or control lines should be protected with a suitable Lightning Barrier from the ESP D or E Series. Protectors for the power supply to

individual cameras (e.g. ESP 240-16A) and the mains supply to the control room (e.g. ESP 240 D1) are available. For coaxial RF (ESP RF Series) cable protectors

and CATV systems (ESP CATV/F) are also available.

Series connection for ESP CCTV/T

DIRTY

CLEAN

From line

To equipment

Earth

Full product range order codes can be found on pages 17/8-17/9