Table of Contents Table of Contents
Previous Page  285 / 336 Next Page
Information
Show Menu
Previous Page 285 / 336 Next Page
Page Background

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

14/13

14

ESP TV Series - Technical specification

Electrical specification

ESP CATV/F

ESP MATV/F

ESP SMATV/F

ESP TV/F

ESP TV/EURO

ABB order code

7TCA085400R0122 7TCA085450R0000 7TCA085450R0026 7TCA085450R0028 7TCA085450R0027

Maximum working voltage

(1)

140 V

18.9 V

18.9 V

6.4 V

6.4 V

Maximum operating current

4 A

800 mA

800 mA

300 mA

300 mA

Characteristic impedance

75 Ω

Bandwidth

5-860 MHz

5-2450 MHz

860-2450 MHz

5-860 MHz

5-860 MHz

Insertion loss:

– 5-860 MHz

< 0.5 dB

< 0.3 dB

< 0.3 dB

< 0.3 dB

– 860-2150 MHz

< 1.5 dB

< 1.5 dB

– 2150-2450 MHz

< 2.2 dB

< 2.2 dB

Return loss (VSWR):

– 5-860 MHz

> 20 dB (< 1.2:1) > 32 dB (< 1.05:1) –

> 32 dB (< 1.05:1) > 32 dB (< 1.05:1)

– 860-2150 MHz

> 20 dB (< 1.2:1) > 20 dB (< 1.2:1) –

– 2150-2450 MHz

< 2.2 dB

< 2.2 dB

Transient specification

ESP CATV/F

ESP MATV/F

ESP SMATV/F

ESP TV/F

ESP TV/EURO

Let-through voltage (all conductors)

(2)

U

p

C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to

BS EN/EN/IEC 61643-21

270 V

70 V

70 V

65 V

65 V

C1 test 1 kV 1.2/50 μs, 0.5 kA 8/20 μs to

BS EN/EN/IEC 61643-21

265 V

60 V

60 V

50 V

50 V

B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21

245 V

45 V

45 V

30 V

30 V

5 kV, 10/700 μs

(3)

250 V

50 V

50 V

35 V

35 V

Maximum surge current

8/20 μs to ITU-T K.45:2003, IEEE C62.41.2:2002

3 kA

Mechanical specification

ESP CATV/F

ESP MATV/F

ESP SMATV/F ESP TV/F

ESP TV/EURO

Temperature range

-40 to +80 ºC

-40 to +80 ºC

Connection type

F female

Euro-TV

Earth connection

~ 9.5 mm (

3

8

”) diameter earth stud

~ 9.5 mm (3⁄8”) diameter earth stud

Case Material

Diecast

Diecast

Weight: – Unit

0.14 kg

0.14 kg

– Packaged

0.15 kg

0.15 kg

Dimensions

See diagram below

(1)

Maximum working voltage (DC or AC peak) measured at

< 5 μA (ESP CATV/F) and < 50 mA (ESP MATV/F,

ESP SMATV/F, ESP TV/EURO, ESP TV/F)

(2)

The maximum transient voltage let-through of the protector

throughout the test (±10%), line to line & line to earth.

Response time < 10 ns

(3)

Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,

K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,

ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)

75 mm

64.5 mm

58 mm

M4 clearance holes,

Depth = 23 mm

Specific systems protection

ESP TV Series