ESP TV Series - Technical specification
Electrical specification
ESP CATV/F
ESP MATV/F
ESP SMATV/F
ESP TV/F
ESP TV/EURO
ABB order code
7TCA085400R0122 7TCA085450R0000 7TCA085450R0026 7TCA085450R0028 7TCA085450R0027
Maximum working voltage
(1)
140 V
18.9 V
18.9 V
6.4 V
6.4 V
Maximum operating current
4 A
800 mA
800 mA
300 mA
300 mA
Characteristic impedance
75 Ω
Bandwidth
5-860 MHz
5-2450 MHz
860-2450 MHz
5-860 MHz
5-860 MHz
Insertion loss:
– 5-860 MHz
< 0.5 dB
< 0.3 dB
–
< 0.3 dB
< 0.3 dB
– 860-2150 MHz
–
< 1.5 dB
< 1.5 dB
–
–
– 2150-2450 MHz
–
< 2.2 dB
< 2.2 dB
–
–
Return loss (VSWR):
– 5-860 MHz
> 20 dB (< 1.2:1) > 32 dB (< 1.05:1) –
> 32 dB (< 1.05:1) > 32 dB (< 1.05:1)
– 860-2150 MHz
–
> 20 dB (< 1.2:1) > 20 dB (< 1.2:1) –
–
– 2150-2450 MHz
–
< 2.2 dB
< 2.2 dB
–
–
Transient specification
ESP CATV/F
ESP MATV/F
ESP SMATV/F
ESP TV/F
ESP TV/EURO
Let-through voltage (all conductors)
(2)
U
p
C2 test 4 kV 1.2/50 μs, 2 kA 8/20 μs to
BS EN/EN/IEC 61643-21
270 V
70 V
70 V
65 V
65 V
C1 test 1 kV 1.2/50 μs, 0.5 kA 8/20 μs to
BS EN/EN/IEC 61643-21
265 V
60 V
60 V
50 V
50 V
B2 test 4 kV 10/700 μs to BS EN/EN/IEC 61643-21
245 V
45 V
45 V
30 V
30 V
5 kV, 10/700 μs
(3)
250 V
50 V
50 V
35 V
35 V
Maximum surge current
8/20 μs to ITU-T K.45:2003, IEEE C62.41.2:2002
3 kA
Mechanical specification
ESP CATV/F
ESP MATV/F
ESP SMATV/F ESP TV/F
ESP TV/EURO
Temperature range
-40 to +80 ºC
-40 to +80 ºC
Connection type
F female
Euro-TV
Earth connection
~ 9.5 mm (
3
⁄
8
”) diameter earth stud
~ 9.5 mm (3⁄8”) diameter earth stud
Case Material
Diecast
Diecast
Weight: – Unit
0.14 kg
0.14 kg
– Packaged
0.15 kg
0.15 kg
Dimensions
See diagram below
(1)
Maximum working voltage (DC or AC peak) measured at
< 5 μA (ESP CATV/F) and < 50 mA (ESP MATV/F,
ESP SMATV/F, ESP TV/EURO, ESP TV/F)
(2)
The maximum transient voltage let-through of the protector
throughout the test (±10%), line to line & line to earth.
Response time < 10 ns
(3)
Test to IEC 61000-4-5:2006, ITU-T (formerly CCITT) K.20,
K.21 and K.45,Telcordia GR-1089-CORE, Issue 2:2002,
ANSI TIA/EIA/IS-968-A:2002 (formerly FCC Part 68)
75 mm
64.5 mm
58 mm
M4 clearance holes,
Depth = 23 mm
Specific systems protection
ESP TV Series