14/18

Total Solution to Earthing & Lightning Protection |

9AKK106354A3360

14

Combined Category D, C, B tested protector (to BS EN 61643) suitable for RF

systems (of power up to 150 W) using coaxial cables at frequencies between 50

MHz and 2.7 GHz to provide effective protection without impairing system

performance. For use at boundaries up to LPZ

0

to protect against flashover

(typically the service entrance location) through to LPZ 3 to protect sensitive

electronic equipment.

Specific systems protection

ESP RF Series

Installation

In a building, connect in series with the coaxial cable near

where it enters or leaves the structure, or close to the equipment

being protected. This should be as close as possible to the

system’s earth star point (to enable a good connection to earth).

On a mast, connect in series with the coaxial cable near the

antenna/dish being protected. Install in a radio communications

room, an existing cabinet or a suitable enclosure.

Accessories

ESP RF BK1

Straight mounting plates

ESP RF BK2

90° angled mounting plates

ESP RF BK3

Bulkhead through mounting plate (single)

ESP RF BK4

Bulkhead through mounting plate

(for 4 products)

ESP RF GDT-A

Replacement gas discharge tube

Full product range order codes can be found on pages 17/8-17/9

ESP RF AA1A11 with 7/16 DIN female

connectors installed in series

DIRTY

CLEAN

From line

Earth

To equipment

ESP RF 111A11 with N female connectors installed

in series

DIRTY

CLEAN

From line

To equipment

Earth

ESP RF 441A11 with BNC female connectors

installed in series

DIRTY

CLEAN

From line

Earth

To equipment

Features & benefits

–– Very low let-through voltage (enhanced protection to

IEC/BS EN 62305) between all lines - Full Mode protection

–– Full Mode design capable of handling partial lightning currents

as well as allowing continual operation of protected equipment

–– Repeated protection in lightning intense environments

–– Superior transient protection to both Gas Discharge Tube

(GDT) and Quarter Wave Stub (QWS) based protectors

–– Very low attenuation and near unity VSWR over a wide

range of frequencies ensure the protectors do not impair

system performance

–– Wide bandwidth means a single product is suitable for a

range of applications

–– Available with N, 7/16 DIN and BNC connectors

–– Easily mounted and earthed via fixtures on the base

of the unit that accept M3 and M5 screws or via

mounting brackets

–– Additional mounting plates give increased flexibility

–– Robust white bronze plated aluminium housing (silver

plate option)

Application

Use on coaxial cables to protect RF transmitter and receiver

systems, including electronics located at the antenna

or dish. Typical examples include cell sites, military

communications, satellite earth stations, pager systems

and emergency services communications systems.

NOTE:

The high level of protection offered by these units comes from the addition of a high pass filter circuit which gives a very low letthrough voltage. It should be

noted that due to this high pass filter circuit no DC power can pass along the transmission line. This is referred to as “DC blocked”. Protectors with other

connectors are available. For RF applications where DC power is present on the coaxial cable, use the alternative RF protectors. The ESP CCTV/B and ESP

CCTV/T are suitable for use on coaxial (or twisted pair) CCTV lines. For coaxial CATV lines, use the ESP CATV/F.