ESP KS & KE Series

For PSTN and U interface ISDN lines on LSA-PLUS modules, use the ESP KT1 or ESP K10T1. For

S/T interface ISDN lines on LSA-PLUS modules, use the ESP KT2 or ESP K10T2. For individual

twisted pair data or signal lines, use the ESP D, E or H Series Lightning Barriers. The ESP SL

and ESP Q Series Lightning Barriers are suitable for high density data and signal lines.

Single line protectors installed on LSA-PLUS

disconnection modules, via ESP KE10 earth

bars, on all incoming signal and data lines

Low cost protection for large numbers of data and signal lines

Very low let-through voltage (enhanced protection to BS EN 62305)

between all lines - Full Mode protection

Full mode design capable of handling partial lightning currents as well

as allowing continual operation of protected equipment

Repeated protection in lightning intense environments

Colour of housing distinguishes electrically different protectors to

help avoid confusion when installed with other protectors (e.g. the

ESP KT1/2) on the same distribution frame

Quick and easy plug-in installation

Protect only the lines you need

Ridged finger holds make it easy to obtain a firm grip for installation

or removal

Use the ESP KE10 to provide trouble free earthing for up to

ten protectors (per disconnection module)

Features and benefits

Combined Category D, C, B tested protector (to BS EN 61643)

suitable for use on ten line LSA-PLUS disconnection modules to

protect individual twisted pair data or signal lines. For use at

boundaries up to LPZ

0

B

to protect against flashover (typically the

service entrance location) through to LPZ 3 to protect sensitive

electronic equipment.

Install protectors on all data

communication and signal lines

that enter or leave each building.

All protectors must be installed via

the ESP KE10 earth bar. Identify

the lines requiring protection and

clip the ESP KE10 on to the

disconnection modules’ earth

points. Plug the protector directly

into each disconnection module

requiring protection (ensuring

the correct orientation) for a

series connection.

In the unlikely situation that the

protector is damaged, it will

sacrifice itself and fail short circuit,

taking the line out of commission.

In addition to indicating that the

protector needs replacing, this will

also prevent subsequent transients

from damaging the equipment.

Installation

Use these units to protect signal,

data, control and instrumentation

systems with LSA-PLUS

disconnection modules.

Application

Having pushed the ESP KE10 earth bar on

to the disconnection modules’ earth points,

firmly push an ESP KS06 (or ESP KS15,

ESP KS30 or ESP KS50) into each line/pair

requiring protection