Background Image
Table of Contents Table of Contents
Previous Page  218 / 300 Next Page
Information
Show Menu
Previous Page 218 / 300 Next Page
Page Background

Furse, Wilford Road, Nottingham, NG2 1EB • Tel: +44 (0)115 964 3700 • Email:

enquiry@furse.com

• Web:

www.furse.com

TSC-0912 - 09.10.12

ESP SL 3-Wire Series

NEW

4

5

6

1

2

3

LightningBarrier

From line

LINE

CLEAN

Earth

To equipment

Furse

WilfordRoad,

Nottingham,

NG2 1EB,UK

Clean

Line

30V

37.8V

750mA

1.0Ω

10kA

43.5V

Nominalvoltage

Maxworkingvoltage,U

c

Currentrating

In-line resistance

Max surgecurrent

Let-throughvoltage,U

p

Very low let-through voltage (enhanced protection to BS EN 62305)

between all lines - Full Mode protection

Full mode design capable of handling partial lightning currents as well

as allowing continual operation of protected equipment

Repeated protection in lightning intense environments

Ultra slim 7 mm width ideal for compact protection of large numbers of

lines (e.g. process control installations)

Two stage removable protection module with simple quick release

mechanism allowing partial removal for easy line commissioning and

maintenance as well as full removal for protection replacement

Very low (1

) in-line resistance allows resistance critical applications

(e.g. alarm loops) to be protected

High (500 mA) maximum running current

High bandwidth enables higher frequency (high traffic or bit rate) data

communications

Strong, flame retardant, polycarbonate housing

Built-in innovative DIN rail foot with locking feature for simple

positioning and clip-on mounting to top hat DIN rails

4 mm

2

terminals allow for larger cross section wiring, stranded wires

terminated with ferrules or fitting two wires into a single terminal

Convenient earthing through DIN foot and/or earth terminal

Features and benefits

Combined Category D, C, B tested protector (to BS EN 61643)

suitable for 3-wire signalling applications which require either a

lower in-line resistance, an increased current and/or higher

bandwidth. Also suitable for DC power applications less than

0.5 Amps. Available for working voltages of up to 6, 15, 30, 50

and 110 Volts. For use at boundaries up to LPZ

0

B

to protect against

flashover (typically the service entrance location) through to LPZ 3

to protect sensitive electronic equipment.

Replacement modules

ESP SLXX/3W/M

Standard module replacement

where XX is voltage rating (06,

15, 30, 50 or 110)

ESP SL/3W/B

Base replacement

For suitable enclosures for the

ESP SL 3-wire Series, please

contact us.

Accessories

Connect in series with the data

communication or signal line

either near where it enters or

leaves the building or close to the

equipment being protected (e.g.

within its control panel). Either

way, it must be very close to the

system’s earth star point. Install

protectors either within an

existing cabinet/cubicle or in a

separate enclosure.

Installation

Use these protectors for 3-wire

systems where installation space is

at a premium and large numbers

of lines require protection (e.g.

process control, high speed digital

communication equipment or

systems with long signal lines).

Application

500 mA