Background Image
Table of Contents Table of Contents
Previous Page  395 / 413 Next Page
Information
Show Menu
Previous Page 395 / 413 Next Page
Page Background

9/7

Modicon Premium automation

platform

9

Power consumption table

Reference

Format

Number

Consumption in mA

(1)

Rack no.

S: single

5

V

c

voltage

24

VR

c

voltage 24 V

c

voltage

D: double

Module Total

Module Total

Module Total

Total

carried over from previous page

Current (mA)

Analog I/O

TSX AEY 414

S

660

TSX AEY 420

S

500

TSX AEY 800

S

270

TSX AEY 810

S

475

TSX AEY 1600

S

270

TSX AEY 1614

S

300

TSX ASY 410

S

900

TSX ASY 800

(2)

S

200

300

Safety

TSX PAY 262

S

150

200

TSX CTY 2A

Counting,

motion control,

weighing

S

280

30

TSX CTY 4A

S

330

36

TSX CTY 2C

S

850

15

TSX CCY 1128

S

660

15

TSX CAY 21

S

1100

15

TSX CAY 41

D

1500

30

TSX CAY 22

S

1100

15

TSX CAY 42

D

1500

30

TSX CAY 33

D

1500

30

TSX CFY 11

S

510

50

TSX CFY 21

S

650

100

TSX CSY 84/85/164

D

1800

TSX ISP Y101

S

150

145

Communication TSX ETY 110 WS

(3)

S

800

TSX ETY 110 WS

(4)

S

1200

TSX ETY 4103

S

360

TSX ETY 5103

S

530

TSX WMY 100

S

360

TSX ETC 101

S

400

TSX IBY 100

S

500

TSX PBY 100

S

400

TSX SAY 1000

S

450

TSX SCY 11601

S

350

TSX SCY 21601

S

350

TSX SCP 111

140

TSX SCP 112

120

TSX SCP 114

150

TSX FPP 10

330

TSX FPP 20

330

TSX MBP 100

220

TSX CPP 110

60

TSX PACC 01

150

Terminal

T FTX 117 ADJ 02

310

Total of

3

powers

Power consumption

Total current (mA)

x 5 V

x 24 VR

x 24 V

Power (mW)

+

+

=

Available power in mW

Overall

Selection of power

supply modules

TSX PSY 1610M

S

24

V

c

non-isolated 15,000

15,000

30,000

TSX PSY 2600M

S

100…240

V

a

25,000

15,000

12,000 26,000

TSX PSY 3610M

D

24

V

c

non-isolated 35,000

19,000

50,000

TSX PSY 5520M

D

24…48

V

c

isolated 35,000

19,000

50,000

TSX PSY 5500M

D

100…120

V

a

200…240

V

a

35,000

19,000

19,000 50,000

TSX PSY 8500M

D

100…120

V

a

200…240

V

a

75,000

38,000 77,000

(5)

(1)

Typical value given for 100% of inputs or outputs at state 1.

(2)

If a 24 VR

c

external power supply is used, the 300 mA consumption on the internal 24 VR should not be taken into account when selecting the rack power supply.

(3)

Without remote power supply (RJ45).

(4)

With remote power supply (AUI).

(5) 77,000

mW at 60°C, 85,000 mW at 55°C or 100,000 mW at 55°C when using

TSX FAN

pp

P

fan modules.

Document for selecting

TSX PSY power supply

modules

(

template to be photocopied)

2

1

3

4

5

6

7

8

9

10