9/6
The power required to supply each TSX RKY rack depends on the type and number of modules installed in the rack. It is therefore necessary to
draw up a power consumption table rack by rack in order to determine the TSX PSY power supply module most suitable for each rack.
The table below can be used to draw up the power consumption table for the three different voltages to be supplied (5 V
c
, 24
V
c
and 24 VR
c
).
Procedure:
b
Check and select a power supply module corresponding to the powers available for the three voltages.
b
Check that the sum of the absorbed powers on these three voltages does not exceed the overall power of the power supply module.
b
Values to be entered according to the type of Premium PLC configuration
Reference
Format
Number
Consumption in mA
(1)
Rack no.
S: single
5
V
c
voltage
24
VR
c
voltage 24 V
c
voltage
D: double
Module Total
Module Total
Module Total
Unity processors
with memory
expansion card
TSX P57 104M
S
850
TSX P57 1634M
D
1650
TSX P57 154M
S
930
TSX P57 204M
D
850
TSX P57 2634M
D
1650
TSX P57 254M
D
930
TSX H57 24M
D
1880
TSX P57 304M
D
1100
TSX P57 3634M
D
1900
TSX P57 354M
D
1180
TSX P57 454M
D
1680
TSX P57 4634M
D
1880
TSX H57 44M
1880
TSX P57 554M
D
1680
TSX P57 5634M
D
1680
TSX P57 6634M
D
1880
PL7 processors
with memory
expansion card
TSX P57 103M
S
440
TSX P57 153M
S
8530
TSX P57 203M
D
750
TSX P57 2623M
D
1110
TSX P57 253M
D
820
TSX P57 2823M
D
1180
TSX P57 303AM
D
1000
TSX P57 3623AM
D
1360
TSX P57 353AM
D
1060
TSX P57 353LAM
S
1650
TSX P57 453AM
D
1080
TSX P57 4823AM
D
1440
Discrete I/O
TSX DEY 08D2
S
55
80
TSX DEY 16A2
S
80
TSX DEY 16A3
S
80
TSX DEY 16A4
S
80
TSX DEY 16A5
S
80
TSX DEY 16D2
S
80
135
TSX DEY 16D3
S
80
135
TSX DEY 16FK
S
250
75
TSX DEY 32D2K
S
135
160
TSX DEY 32D3K
S
140
275
TSX DEY 64D2K
S
155
315
TSX DSY 08R4D
S
55
80
TSX DSY 08R5
S
55
70
TSX DSY 08R5A
S
55
80
TSX DSY 08S5
S
125
TSX DSY 08T2
S
55
TSY DSY 08T22
S
55
TSX DSY 08T31
S
55
TSX DSY 16R5
S
80
135
TSX DSY 16S4
S
220
TSX DSY 16S5
S
220
TSX DSY 16T2
S
80
TSX DSY 16T3
S
80
TSX DSY 32T2K
S
140
TSX DSY 64T2K
S
155
TSX DMY 28FK
S
300
75
TSX DMY 28RFK
S
300
75
Bus X remote
TSX REY 200
S
500
Total
to be carried over to next page
Current (mA)
Modicon Premium automation
platform
9
Power consumption table
Document for selecting
TSX PSY power supply
modules
(
template to be photocopied)
2
1
3
4
5
6
7
8
9
10