Architectures
Typical architecture
In this type of architecture the I/O system of Premium PLCs equipped with the
TSX
H57 24M/44M
dedicated Hot Standby processor is defined by distribution of field
products or devices on the Ethernet Modbus/TCP network.
Functionally, the products or devices connected on the same Ethernet Modbus/TCP
network can be either of the following types:
b
Client: Twido controller, Modicon PLC, Magelis HMI, W@de remote management
module, etc.
b
Modbus/TCP server: Modicon OTB/Momentum distributed I/O, Modicon STB I/O
islands, Altivar variable speed drives, Lexium servo drives, Inductel/Ositrack
identification systems, etc.
The Ethernet I/O Scanning service allows client-server type exchanges between the
PLC and Ethernet devices communicating in Modbus/TCP protocol. This service can
be used to configure up to 64 stations with periodic read and/or write exchanges
based on the tables of variables (word type) for the target products or devices. The
I/O Scanning service is a function available as standard with
TSX ETY 4103/5103
Ethernet network modules.
The topology of the Ethernet Modbus/TCP network providing the connection
between the PLC Ethernet Modbus/TCP modules and the distributed products/
devices can be bus or ring type with a copper cable or fibre optic medium.
“
Monitored” Ethernet network modules
When the Hot Standby system is configured with Unity Pro software, an Ethernet
module
no.
4-
M
for each Primary PLC and Standby PLC must always be defined
with “monitored” status and have the Ethernet I/O Scanning service.
This status assigns the module with monitoring of both its correct operation and its
electrical connection to its Ethernet switch. A failure (of the “monitored” module or its
Ethernet connection) triggers the changeover from the Primary PLC to the Standby
PLC.
10
10
10
10
10
15
17
18
19
10
10
10
10
13
2
1
11
3 4-
M 4
2 3 4-
M 4
13
12
12
16
12
SCADA
Vijeo Citect
Monitor Pro
Ethernet Modbus/TCP ring
(
dedicated to SCADA)
Primary
Premium
Standby
Premium
CPU Sync link
Ethernet Modbus/TCP ring
(
I/O Scanning service)
Modicon M340
Modicon STB
Altivar
61
Modicon
OTB
Magelis
XBT GT
Architectures
Presentation:
page 4/52
Description:
page 4/53
Functions:
pages 4/58 ...
References:
pages 4/60 ...
Redundant components
1
Non-expandable rack with 6, 8 or 12 positions
TSX RKY
pp
(
single-rack configuration) or expandable with 4, 6, 8 or 12
positions
TSX RKY
pp
EX
(
multi-rack configuration)
2
Power supply module
TSX PSY
ppp
M
3
Premium Hot Standby processor
TSX H57 24M/44M
4
Ethernet Modbus/TCP network module
TSX ETY 4103/5103
(
version
u
sv 4.0)
4-
M
“
Monitored” Ethernet Modbus/TCP network module
TSX ETY 4103/5103
(
version
u
sv 4.0)
Shared components on the Ethernet Modbus/TCP ring
15
Modicon M340 automation platform with processor with
integrated Ethernet port
BMXP34 2020/2030
16
Modicon STB modular distributed I/O with network interface
module
STB NIP 2212
17
Altivar 61/71 variable speed drive with communication card
VW3 A3 310
18
Optimum Modicon OTB distributed I/O, with interface
module
OTB 1E0 DM9LP
19
Magelis XBT GT graphic display terminal with embedded
Ethernet port
XBT GT
pp
30/40
Other possible shared components:
-
Modicon FTM IP 67 modular I/O
-
Momentum distributed I/O
-
TSX ETG 100/1000
gateway for connecting Modbus products
-
W@de remote management modules (RTU) for the water
sector
TSX HEW 315/320/330
-
Inductel/Ositrack identification system
XGK S1715503
and
XGK Z33ETH
-
Lexium servo drives with communication card
AMO ETH 001V000
-
Preventa
XPS MF
compact and modular safety PLCs
Ethernet cabling components:
10
ConneXium managed switch 2, 4 or 8 ports
10/100
BASE-TX
TCS ESM 0
p
3
11
CPU Sync link, copper crossover cable
490
NTC 000
ppp
12
Copper straight-through cable
490
NTW 000
ppp
13
Copper crossover cable
490
NTC 000
ppp
(1)
(1)
For Ethernet ring lengths > 100 m, the copper link is
replaced by a fibre optic link, either multimode (3 km max.)
or single-mode (20 km max.) via ConneXium switches
TCS ESM 043F2CS0
and straight-through copper cable
490
NTW 000
ppp
(
fibre optic not supplied by Schneider
Electric).
Note
:
Should other Primary and Standby PLC Ethernet modules
be required to be “monitored”, in order to increase the redundant
equipment covered (for example for the SCADA Ethernet
network), an application program must be written in each PLC.
Modicon Premium automation
platform
Hot Standby system
Unity Pro software
2
1
3
4
5
6
7
8
9
10