4/54

Architectures

Typical architecture

In this type of architecture the I/O system of Premium PLCs equipped with the

TSX

H57 24M/44M

dedicated Hot Standby processor is defined by distribution of field

products or devices on the Ethernet Modbus/TCP network.

Functionally, the products or devices connected on the same Ethernet Modbus/TCP

network can be either of the following types:

b

Client: Twido controller, Modicon PLC, Magelis HMI, W@de remote management

module, etc.

b

Modbus/TCP server: Modicon OTB/Momentum distributed I/O, Modicon STB I/O

islands, Altivar variable speed drives, Lexium servo drives, Inductel/Ositrack

identification systems, etc.

The Ethernet I/O Scanning service allows client-server type exchanges between the

PLC and Ethernet devices communicating in Modbus/TCP protocol. This service can

be used to configure up to 64 stations with periodic read and/or write exchanges

based on the tables of variables (word type) for the target products or devices. The

I/O Scanning service is a function available as standard with

TSX ETY 4103/5103

Ethernet network modules.

The topology of the Ethernet Modbus/TCP network providing the connection

between the PLC Ethernet Modbus/TCP modules and the distributed products/

devices can be bus or ring type with a copper cable or fibre optic medium.

Monitored” Ethernet network modules

When the Hot Standby system is configured with Unity Pro software, an Ethernet

module

no.

4-

M

for each Primary PLC and Standby PLC must always be defined

with “monitored” status and have the Ethernet I/O Scanning service.

This status assigns the module with monitoring of both its correct operation and its

electrical connection to its Ethernet switch. A failure (of the “monitored” module or its

Ethernet connection) triggers the changeover from the Primary PLC to the Standby

PLC.

10

10

10

10

10

15

17

18

19

10

10

10

10

13

2

1

11

3 4-

M 4

2 3 4-

M 4

13

12

12

16

12

SCADA

Vijeo Citect

Monitor Pro

Ethernet Modbus/TCP ring

(

dedicated to SCADA)

Primary

Premium

Standby

Premium

CPU Sync link

Ethernet Modbus/TCP ring

(

I/O Scanning service)

Modicon M340

Modicon STB

Altivar

61

Modicon

OTB

Magelis

XBT GT

Architectures

Presentation:

page 4/52

Description:

page 4/53

Functions:

pages 4/58 ...

References:

pages 4/60 ...

Redundant components

1

Non-expandable rack with 6, 8 or 12 positions

TSX RKY

pp

(

single-rack configuration) or expandable with 4, 6, 8 or 12

positions

TSX RKY

pp

EX

(

multi-rack configuration)

2

Power supply module

TSX PSY

ppp

M

3

Premium Hot Standby processor

TSX H57 24M/44M

4

Ethernet Modbus/TCP network module

TSX ETY 4103/5103

(

version

u

sv 4.0)

4-

M

Monitored” Ethernet Modbus/TCP network module

TSX ETY 4103/5103

(

version

u

sv 4.0)

Shared components on the Ethernet Modbus/TCP ring

15

Modicon M340 automation platform with processor with

integrated Ethernet port

BMXP34 2020/2030

16

Modicon STB modular distributed I/O with network interface

module

STB NIP 2212

17

Altivar 61/71 variable speed drive with communication card

VW3 A3 310

18

Optimum Modicon OTB distributed I/O, with interface

module

OTB 1E0 DM9LP

19

Magelis XBT GT graphic display terminal with embedded

Ethernet port

XBT GT

pp

30/40

Other possible shared components:

-

Modicon FTM IP 67 modular I/O

-

Momentum distributed I/O

-

TSX ETG 100/1000

gateway for connecting Modbus products

-

W@de remote management modules (RTU) for the water

sector

TSX HEW 315/320/330

-

Inductel/Ositrack identification system

XGK S1715503

and

XGK Z33ETH

-

Lexium servo drives with communication card

AMO ETH 001V000

-

Preventa

XPS MF

compact and modular safety PLCs

Ethernet cabling components:

10

ConneXium managed switch 2, 4 or 8 ports

10/100

BASE-TX

TCS ESM 0

p

3

11

CPU Sync link, copper crossover cable

490

NTC 000

ppp

12

Copper straight-through cable

490

NTW 000

ppp

13

Copper crossover cable

490

NTC 000

ppp

(1)

(1)

For Ethernet ring lengths > 100 m, the copper link is

replaced by a fibre optic link, either multimode (3 km max.)

or single-mode (20 km max.) via ConneXium switches

TCS ESM 043F2CS0

and straight-through copper cable

490

NTW 000

ppp

(

fibre optic not supplied by Schneider

Electric).

Note

:

Should other Primary and Standby PLC Ethernet modules

be required to be “monitored”, in order to increase the redundant

equipment covered (for example for the SCADA Ethernet

network), an application program must be written in each PLC.

Modicon Premium automation

platform

Hot Standby system

Unity Pro software

2

1

3

4

5

6

7

8

9