5.39
Sales Service Centre • 01952 675612 Technical Support Helpline • 01952 675689
Contactors & Relays cont.
Lamp Power 16A 25A
16A + 25A + 40A 63A
Compact fluo lamps
Compact fluo lamp with
external electronic ballast
5W
11
15
17
27
49
76
7W
11
15
17
27
49
76
9W
9
13
16
26
40
63
11W
9
13
16
26
40
63
15W
7
11
14
22
36
57
18W
7
11
14
22
36
57
20W
7
11
14
22
36
57
23W
7
11
14
22
36
57
26W
7
11
14
22
36
57
Compact fluo lamp with
integrated electronic ballast
5W
17
27
34
54
86
135
7W
17
27
34
54
86
135
9W
17
27
34
54
86
135
11W
17
27
34
54
86
135
15W
17
27
34
54
86
135
18W
13
20
25
40
63
100
20W
13
20
25
40
63
100
23W
13
20
25
40
63
100
26W
13
20
25
40
63
100
Incandescent lamps
Tungsten & halogen lamps
230V
40W
32
50
36
57
76
120
60W
21
33
28
45
67
105
75W
17
27
24
38
63
100
100W 13
20
17
28
41
65
150W 8
13
11
18
29
45
200W 6
9
8
14
22
35
300W 4
7
6
10
15
23
500W 2
3
3
6
9
14
1000W 0
0
1
2
4
7
Tungsten & halogen lamps
12 ou 24V
20W
13
20
25
40
139 218
35W
8
13
16
26
82
129
50W
6
9
11
18
60
94
75W
4
6
7
12
52
82
100W 2
3
3
6
35
55
150W 1
2
2
4
20
31
LED
LED 230V with integrated
electronic ballast - non
dimmable
4W
17
27
34
54
86
135
4.5W
17
27
34
54
86
135
6W
17
27
34
54
86
135
7W
17
27
34
54
86
135
8W
17
27
34
54
86
135
12W
17
27
34
54
86
135
17W
13
20
25
40
63
101
18W
13
20
25
40
63
101
22W
13
20
25
40
63
101
30W
9
14
17
28
44
70
34W
9
14
17
28
44
70
40W
9
14
17
28
44
70
50W
7
11
14
22
35
55
LED 230V with integrated
electronic ballast - dimmable
4W
38
60
76
120 159 250
5.5W
38
60
76
120 159 250
6W
38
60
76
120 159 250
7W
38
60
76
120 159 250
8W
38
60
76
120 159 250
12W
38
60
76
120 159 250
17W
28
44
56
88
118 185
18W
28
44
56
88
118 185
22W
28
44
56
88
118 185
30W
20
31
39
62
82
130
34W
20
31
39
62
82
130
40W
20
31
39
62
82
130
50W
16
24
30
48
65
102
LED 230V headlight with
integrated electronic ballast
100W -
-
3
5
6
9
150W -
-
1
3
4
6
200W -
-
1
2
4
6
LED 12V with separated
transformer - dimmable
1W
38
60
76
120 180 220
2.5W
38
60
76
120 180 220
4W
38
60
76
120 180 220
5W
38
60
76
120 180 220
7W
38
60
76
120 160 200
10W
38
60
76
120 160 200
15W
28
44
56
88
160 200
Fluorescent tubes
T5 single - uncompensated 15W
13
20
19
30
70
100
18W
13
20
19
30
70
100
20W
12
19
19
30
70
100
36W
12
15
17
28
60
90
40W
10
13
16
26
60
90
42W
9
12
15
24
55
83
58W
7
9
10
17
35
56
65W
6
8
10
17
35
56
80W
5
7
9
15
30
48
115W 4
5
6
10
20
32
140W 3
5
6
10
16
26
T5 single - paralell
compensation
15W
7
11
12
20
36
57
18W
7
11
12
20
36
57
20W
7
11
12
20
36
57
36W
7
11
12
20
34
53
40W
7
11
12
20
29
45
42W
7
11
12
20
29
45
58W
6
10
9
15
27
42
65W
6
10
9
15
27
42
80W
6
10
9
15
27
42
115W 6
10
9
15
25
39
Lamp Power 16A 25A
16A + 25A + 40A 63A
Fluorescent tubes
T5 double - uncompensated 2 x 18W 13
20
25
40
50
78
2 x 20W 12
19
24
38
50
78
2 x 36W 12
15
19
30
44
69
2 x 40W 10
13
16
26
40
63
2 x 42W 9
12
15
24
40
63
2 x 58W 7
9
11
18
27
42
2 x 65W 6
8
10
16
27
42
2 x 80W 5
7
8
14
22
35
2 x 115W 4
5
6
10
16
25
T5 double - serie
compensation
2 x 18W 7
11
14
22
34
53
2 x 20W 7
11
14
22
29
45
2 x 36W 6
10
12
20
27
42
2 x 40W 6
10
12
20
27
42
2 x 42W 6
10
12
20
27
42
2 x 58W 6
10
12
20
25
39
2 x 65W 5
7
8
14
23
36
2 x 80W 5
7
8
14
20
31
2 x 115W 4
5
6
10
17
25
T5 single - electronic ballast 15W
7
11
14
22
36
57
18W
7
11
14
22
36
57
20W
7
11
14
22
36
57
36W
7
11
14
22
34
53
40W
7
11
14
22
29
45
42W
7
11
14
22
29
45
58W
6
10
12
20
27
42
65W
6
10
12
20
27
42
80W
6
10
12
20
27
42
115W 6
10
12
20
25
39
T5 double - electronic ballast 2 x 18W 7
11
14
22
34
53
2 x 20W 7
11
14
22
29
45
2 x 36W 6
10
12
20
27
42
2 x 40W 6
10
12
20
27
42
2 x 42W 6
10
12
20
27
42
2 x 58W 6
10
12
20
25
39
2 x 65W 5
7
8
14
23
36
2 x 80W 5
7
8
14
20
31
2 x 115W 4
5
6
10
17
25
Discharge lamps
High-pressure mercury-
vapor lamps - without
compensation
50W
9
14
17
28
32
50
80W
6
9
11
18
24
37
125W 3
5
6
10
18
28
250W 2
3
3
6
10
15
400W 1
1
1
2
6
9
700W 0
0
0
0
4
5
High-pressure mercury-
vapor lamps - paralell
compensation
50W
7
11
14
22
26
40
80W
5
8
10
16
22
34
125W 3
5
6
10
15
23
250W 2
3
3
6
9
14
400W 1
1
1
2
5
8
700W 0
0
0
0
3
5
1000W 0
0
0
0
2
3
Low pressure sodium lamps
- without compensation
18W
8
10
8
12
17
23
35W
4
6
7
9
14
20
55W
3
6
7
9
14
20
90W
2
4
5
6
9
14
135W 1
3
3
4
6
8
180W 1
2
2
4
6
8
Low pressure sodium lamps
- paralell compensation
18W
5
7
5
8
12
24
35W
4
6
4
7
10
23
55W
3
5
3
5
10
19
90W
2
3
3
4
8
16
135W 1
2
1
2
5
7
180W 1
2
1
2
5
6
High pressure sodium lamps
- without compensation
35W
11
14
15
24
30
50
50W
9
12
10
15
22
34
70W
8
9
8
12
18
28
110W 6
8
6
10
14
22
150W 4
7
5
8
10
16
250W 2
4
3
5
6
10
400W 0
1
1
2
4
6
1000W 0
1
1
1
2
3
High pressure sodium-
vapour lamps - electronic
ballast or parallel
compensation
35W
6
9
11
18
31
50
50W
6
9
11
18
22
35
70W
4
6
7
12
16
25
110W 3
5
6
8
13
21
150W 3
5
4
6
8
13
250W 2
3
3
4
7
11
400W 1
1
1
2
5
8
1000W 0
0
0
1
2
3
Metal halide lamps - without
compensation
35W
12
24
19
30
42
55
70W
10
15
12
17
26
36
150W 6
7
8
12
14
20
250W 3
5
5
8
9
14
400W 1
2
2
4
6
9
1000W 0
0
0
0
3
5
Metal halide lamps -
electronic ballast or parallel
compensation
35W
6
10
12
18
22
39
70W
5
8
10
13
22
39
150W 3
5
6
8
12
22
250W 3
5
6
7
9
16
400W 1
1
1
2
5
7
1000W 0
0
0
1
2
3
Lighting systems with electronic ballasts cause inrush current peaks. Therefore we recommend you use the chart below to determinate the maximum amount of
lamps that can be connected to a Hager contactor: The chart gives the maximum amount of lamps per contact. In 2014 the performances of the contactors in
combination with lights increased. The products identified on the front face with the ‘+’ can accept a higher number of lamps. For these products, see the figures in
the column with the ‘+’ in the header.
Modular
Devices