17/100 Circuit-breakers, switch-disconnectors
Terminals
2010 CA08103002Z-EN
www.eaton.comTerminals
Space requirement
Rated
current
1)
Number
of poles
For use
with
Terminal capacity
Terminal capacity
Cable
Cable
lugs
Terminal
capacity
AWG/kcmil
Copper strip
No. of discs ×
width × disc
thickness
Copper bar
width x
thickness
I
n
A
mm²
mm
mm
Connection width extension
–
Max.
1600
3 pole NZM4,
N(S)4
Copper
cable lugs
4 x 300
6 x 95-240
4 x 600
6 x 000-500
max. (2 x)
10 x 80 x 1.0
max. (2 x)
80 x 10
–
–
Max.
1600
4 pole NZM4-4,
N4-4
–
With two threaded studs
–
1600
3 pole NZM4,
N(S)4
Copper
cable lugs
4 x 95-300 4 x 500
(2x)
10 x 80 x 1.0
(2 x) 10 x 80
Notes
1)
The rated operational current values have been determined according to IEC/EN 60947 (switchgear standard). They generally
relate to the max. defined cross-sections and are intended as a general guide.
The engineering standards which apply in each case must be observed.
25
50
20
o
10.5
o
10.5
25
50
20
o
10.5
o
10.5
NZM4
HPL17100EN