Transformers

Single-phase multi-winding transformers

2010

CA08103002Z-EN

www.eaton.com

15/9

Single-phasemulti-winding transformers

Rated

output

Rated

input

voltage

Rated

output

voltage

Part no.

Article no.

Price

See

price list

Std. pack

Notes

kVA V

V

Single-phase multi-winding transformers

(

Universal) control, isolating and safety transformers

to VDE 0550,

IEC/EN 61558-2-2/2-4/2-6

VDE 0570 Part 2-2, Part 2-6 (safety transformers),

Part 2-4 (isolating transformers)

0.1

208

230

380

400

415

440

460

480

500

525

550

575

600

2

x 115

UTI0.1-115

206923

1

off

Transformer-protective

circuit-breakers PKZM0-...-T

→Page 7/6

0.2

UTI0.2-115

206924

0.315

UTI0.315-115

206925

0.5

UTI0.5-115

206926

0.63

UTI0.63-115

206927

0.8

UTI0.8-115

206928

1

UTI1.0-115

206929

Rated

output

Max. output

current

Part no.

Article no.

Price

See

price list

Std.

pack

Notes

kVA

A

Multipurpose power supply units AING

Safety transformer to IEC/EN 61558-2-2/2-6

VDE 0570 Part 2-2/2-6

For every output voltage a fuse, an LED and a

changeover contact for monitoring and annunciation.

Non-standard voltages please enquire

Rated input voltage 230 ± 5 % V

Rated output voltage 24 AC, 10 DC, 24 DC V

0.1

4.2

1

3

AING4

269516

1

off

•

Circuit diagram:

Signal contacts

Switching voltage max. 250 V AC/110 V DC

max. 1 A

Switching duty 62 VA/30 W

LED indicators

•

Output voltage present: LED = green

•

Fuse fault/missing: LED = red

Size/type FK2 fuses are used.

0.192

8

1

3

AING8

269517

Notes

Information relevant for export to North America

Product Standards

UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06;

IEC/EN 61558-2-2; CE marking

UL File No.

E167225

UL CCN

XPTQ2, XPTQ8

CSA File No.

UL report applies to both US and Canada

CSA Class No.

–

NA Certification

UL Recognized, certified by UL for use in Canada

Suitable for

Branch circuits

Max. Voltage Rating

600

V AC

Degree of Protection

IEC: IP00, UL/CSA Type: -

+5 %

230

V

–5 %

0

24

V AC

+10 V DC

_

+24 V DC

_

0

UTI, AING