Control relays, multi-function display
Switched-mode power supply units
2010
CA08103002Z-EN
www.eaton.com...POW
12/49
...POWSwitched-modepower supplyunits
EASY200-POW EASY400-POW EASY500-POW EASY600-POW
EASY430-POW
General
Standards
EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27, EN 61000-6-2
Dimensions (W x H x D)
mm 35.5 x 90 x 58
(2
space units)
71.5
x 90 x 58
(4
space units)
71.5
x 90 x 58
(4
space units)
107.5
x 90 x 58
(6
space units)
Weight
kg
0.1
0.25
0.28
0.3
Mounting
Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1
(
accessories).
Terminal capacity
Solid
mm
2
0.2 - 4 (
AWG 22 - 12)
Flexible with ferrule
mm
2
0.2 - 2.5 (
AWG 22 - 12)
Flat-blade screwdriver
mm 3.5 x 0.8
3.5
x 0.8
3.5
x 0.8
3.5
x 0.8
Max. tightening torque
Nm
0.6
0.6
0.6
0.6
Ambient climatic conditions
Operating ambient temperature
°C
-25…55,
low
temperatures to
IEC 60068-2-1,
high temperatures
to IEC 60068-2-2
-25…55,
low
temperatures to
IEC 60068-2-1,
high temperatures
to IEC 60068-2-2
-25 - 55,
low
temperatures to
IEC 60068-2-1,
high temperatures
to IEC 60068-2-2;
-25 - 45
to UL/CSA
-25…55,
low
temperatures to
IEC 60068-2-1,
high temperatures
to IEC 60068-2-2
Condensation
Prevent condensation by means of suitable measures
Storage
°C
-40 - 70
-40 - 70
-40 - 70
-40 - 70
Relative humidity, non-condensing (IEC/EN 60068-2-30)
%
5 - 95
5 - 95
5 - 95
5 - 95
Air pressure (in operation)
hPa
795 - 1080
795 - 1080
795 - 1080
795 - 1080
Max. installation altitude above sea level,
observe derating at higher altitudes
m
2000
2000
2000
2000
Ambient mechanical conditions
Pollution degree
2
2
2
2
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
IP20
IP20
IP20
Vibrations (IEC/EN 60068-2-6)
Constant amplitude 0.15 mm
Hz
10 - 57
10 - 57
10 - 57
10 - 57
Constant acceleration, 2 g
Hz
57 - 150
57 - 150
57 - 150
57 - 150
Mechanical shock resistance (IEC/EN 60068-2-27)
semi-sinusoidal 15 g/11 ms
Shocks 18
18
18
18
Drop to IEC/EN 60068-2-31
Drop
height
mm 50
50
50
50
Free fall, packaged (IEC/EN 60068-2-32)
m
1
1
1
1
Mounting position
Vertical or
horizontal
Vertical or
horizontal
Horizontal,
terminals at top
Horizontal,
terminals at top
Electromagnetic compatibility (EMC)
Electrostatic discharge (ESD), to IEC EN 61000-4-2
Air discharge
kV
8
8
8
8
Contact discharge
kV
6
6
6
6
Electromagnetic fields (RFI), to IEC EN 61000-4-2
V/m 10
10
10
10
Radio interference suppression
EN 55011 Class B; EN 55022 Class B, EN 50081-2 Class B
Burst pulses (IEC/EN 61000-4-4, level 3)
kV
2
2
2
2
Power pulses (surge) (IEC/EN 61000-4-5)
kV
2 (
supply cables, symmetrical)
Power pulses (surge) (IEC/EN 61000-4-5,
Level 2), 24 V
kV
0.5 (
output cables, symmetrical)
Radiated RFI, to IEC/EN 61000-4-6
V
10
10
10
10
Surge voltage (EN 50 178), 24 V
kV
6
6
6
6
Insulation resistance
Clearance in air and creepage distances
EN 50178
Insulation resistance
EN 50178
Protection class U
out
to U
in
Class II to IEC 60536
Potential isolation primary/secondary
Yes, SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178
Input voltage
Rated input voltage AC
V
100/120/230/240 (-15/
+10 %)
Protective switches AC
FAZ-C1/1 or FAZ-B6/1
Rated input voltage DC
V
85 - 264
85 - 264
85 - 264
85 - 264
DC protective switches
FAZ-C2/1-DC
FAZ-C2/1-DC
FAZ-C2/1-DC
FAZ-C2/1-DC
Voltage range
V AC
85 - 264
85 - 264
85 - 264
85 - 264
Frequency range
Hz
47 - 63
47 - 63
47 - 63
47 - 63
Mains failure bridging 115/230 V (IEC/EN 61000-4-11)
ms
> 10/> 20
> 20/> 40
> 20/> 40
> 20/> 40
Fuse 115/230 V
A
1.5
slow
2/1
time delay
2/1
time delay
2/1
time delay