Control relays, multi-function display

Switched-mode power supply units

2010

CA08103002Z-EN

www.eaton.com

...POW

12/49

...POWSwitched-modepower supplyunits

EASY200-POW EASY400-POW EASY500-POW EASY600-POW

EASY430-POW

General

Standards

EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27, EN 61000-6-2

Dimensions (W x H x D)

mm 35.5 x 90 x 58

(2

space units)

71.5

x 90 x 58

(4

space units)

71.5

x 90 x 58

(4

space units)

107.5

x 90 x 58

(6

space units)

Weight

kg

0.1

0.25

0.28

0.3

Mounting

Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1

(

accessories).

Terminal capacity

Solid

mm

2

0.2 - 4 (

AWG 22 - 12)

Flexible with ferrule

mm

2

0.2 - 2.5 (

AWG 22 - 12)

Flat-blade screwdriver

mm 3.5 x 0.8

3.5

x 0.8

3.5

x 0.8

3.5

x 0.8

Max. tightening torque

Nm

0.6

0.6

0.6

0.6

Ambient climatic conditions

Operating ambient temperature

°C

-25…55,

low

temperatures to

IEC 60068-2-1,

high temperatures

to IEC 60068-2-2

-25…55,

low

temperatures to

IEC 60068-2-1,

high temperatures

to IEC 60068-2-2

-25 - 55,

low

temperatures to

IEC 60068-2-1,

high temperatures

to IEC 60068-2-2;

-25 - 45

to UL/CSA

-25…55,

low

temperatures to

IEC 60068-2-1,

high temperatures

to IEC 60068-2-2

Condensation

Prevent condensation by means of suitable measures

Storage

°C

-40 - 70

-40 - 70

-40 - 70

-40 - 70

Relative humidity, non-condensing (IEC/EN 60068-2-30)

%

5 - 95

5 - 95

5 - 95

5 - 95

Air pressure (in operation)

hPa

795 - 1080

795 - 1080

795 - 1080

795 - 1080

Max. installation altitude above sea level,

observe derating at higher altitudes

m

2000

2000

2000

2000

Ambient mechanical conditions

Pollution degree

2

2

2

2

Protection type (IEC/EN 60529, EN50178, VBG 4)

IP20

IP20

IP20

IP20

Vibrations (IEC/EN 60068-2-6)

Constant amplitude 0.15 mm

Hz

10 - 57

10 - 57

10 - 57

10 - 57

Constant acceleration, 2 g

Hz

57 - 150

57 - 150

57 - 150

57 - 150

Mechanical shock resistance (IEC/EN 60068-2-27)

semi-sinusoidal 15 g/11 ms

Shocks 18

18

18

18

Drop to IEC/EN 60068-2-31

Drop

height

mm 50

50

50

50

Free fall, packaged (IEC/EN 60068-2-32)

m

1

1

1

1

Mounting position

Vertical or

horizontal

Vertical or

horizontal

Horizontal,

terminals at top

Horizontal,

terminals at top

Electromagnetic compatibility (EMC)

Electrostatic discharge (ESD), to IEC EN 61000-4-2

Air discharge

kV

8

8

8

8

Contact discharge

kV

6

6

6

6

Electromagnetic fields (RFI), to IEC EN 61000-4-2

V/m 10

10

10

10

Radio interference suppression

EN 55011 Class B; EN 55022 Class B, EN 50081-2 Class B

Burst pulses (IEC/EN 61000-4-4, level 3)

kV

2

2

2

2

Power pulses (surge) (IEC/EN 61000-4-5)

kV

2 (

supply cables, symmetrical)

Power pulses (surge) (IEC/EN 61000-4-5,

Level 2), 24 V

kV

0.5 (

output cables, symmetrical)

Radiated RFI, to IEC/EN 61000-4-6

V

10

10

10

10

Surge voltage (EN 50 178), 24 V

kV

6

6

6

6

Insulation resistance

Clearance in air and creepage distances

EN 50178

Insulation resistance

EN 50178

Protection class U

out

to U

in

Class II to IEC 60536

Potential isolation primary/secondary

Yes, SELV (VDE 0100 Part 410; IEC 60364-4-41, HD 384.4.41 S2) EN 60950, EN 50178

Input voltage

Rated input voltage AC

V

100/120/230/240 (-15/

+10 %)

Protective switches AC

FAZ-C1/1 or FAZ-B6/1

Rated input voltage DC

V

85 - 264

85 - 264

85 - 264

85 - 264

DC protective switches

FAZ-C2/1-DC

FAZ-C2/1-DC

FAZ-C2/1-DC

FAZ-C2/1-DC

Voltage range

V AC

85 - 264

85 - 264

85 - 264

85 - 264

Frequency range

Hz

47 - 63

47 - 63

47 - 63

47 - 63

Mains failure bridging 115/230 V (IEC/EN 61000-4-11)

ms

> 10/> 20

> 20/> 40

> 20/> 40

> 20/> 40

Fuse 115/230 V

A

1.5

slow

2/1

time delay

2/1

time delay

2/1

time delay