Connection system SmartWire
2010
CA08103002Z-EN
www.eaton.com8/43
SWIRE-4DI-2DO-R
SWIRE-GW-MB
General
Standards
General
IEC/EN 60947, EN 55011, EN 55022,
IEC/EN 61000-4, IEC/EN 60068-2-27
Mounting
Tophat rail IEC/EN 60715 (35 mm) or screw fixing with fixing brackets
ZB4-101-GF1 (accessories)
Dimensions (w x d x h)
mm 35 x 90 x 74
35
x 90 x 109
Weight
kg
0.12
0.15
Terminal capacity
Solid
mm
2
0.5…1.5
0.5…1.5
Flexible with ferrule
mm
2
0.5…1.5
0.5…1.5
Solid or stranded
AWG 22…16
22…16
Flat-blade screwdriver
mm 3.5 x 0.8
3.5
x 0.8
Max. tightening torque
Nm 0.6
0.6
Ambient climatic conditions
Ambient temperature Operation
°C
-25 -
+55
-25 -
+55
Storage
°C
-25 -
+70
-25 -
+70
Condensation
Prevent condensation by means of suitable measures
Relative humidity, non-condensing (IEC/EN 60068-2-30)
% 5 - 95
5 - 95
Air pressure (in operation)
hPa
795 - 1080
795 - 1080
Ambient mechanical conditions
Protection type (IEC/EN 60529, EN50178, VBG 4)
IP20
IP20
Pollution degree
2
2
Mounting position
Vertical
Vertical
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
Air discharge
kV
8
8
Contact discharge
kV
–
–
Electromagnetic fields (IEC/EN 61000-4-3, RFI)
V/m
10
10
Radio interference suppression (EN 55011, EN 55022)
Class A
Class A
Burst pulses (IEC/EN 61000-4-4, level 3)
Supply cables
kV
2
2
Signal cables
kV
–
2
power pulses (surge) (IEC/EN 61000-4-5, level 2)
kV
0.5 (
supply cables, symmetrical)
Emitted RFI (IEC/EN 61000-4-6)
V
10
10
Insulation resistance
Clearances and creepage distances
EN 50178, EN 60947-1, UL 508, CSA C22.2 No 142
Insulation resistance
EN 50178, EN 60947-1
Supply voltage, gateway electronics and SmartWire station
electronics U
gateway
Rated operational voltage U
gateway
V DC –
24, -15 %,
+20 %
Permissible range
Supply from gateway or power
module
20.4...28.8
Ripple
% –
≦ 5
Maximum gateway current consumption at 24 V DC
mA
–
500 (
normally 100 coupling unit +
normally 25 per SmartWire card)
Voltage dips (IEC/EN 61131-2)
ms
–
10
Heat dissipation at 24 V DC
W –
Normally 6
Protection against polarity reversal
Yes
Short-circuit protection, SmartWire side
–
Yes
Power supply
U
AUX
(
power supply for switching the
SmartWire slaves, e.g. contactor coils)
Rated operational voltage U
AUX
V DC –
24, -15 %,
+20 % (Derating from> 40 °C)
Permissible range
V DC –
20.4…28.8,
at 45 °C: 21…28.8,
at 50 °C: 21.6…28.8,
at 55 °C: 22.2…27.6
Input current U
AUX
at 24 V DC
A
–
Normally 3
Ripple
% –
≦ 5
Voltage dips (IEC/EN 61131-2)
ms
–
10
Protection against polarity reversal
Yes
Voltage
U
s
V
–
Yes
Short-circuit protection, SmartWire side
–
No, external 3 A fuse or FAZ-Z3
SWIRE-…