Connection system SmartWire

2010

CA08103002Z-EN

www.eaton.com

8/43

SWIRE-4DI-2DO-R

SWIRE-GW-MB

General

Standards

General

IEC/EN 60947, EN 55011, EN 55022,

IEC/EN 61000-4, IEC/EN 60068-2-27

Mounting

Tophat rail IEC/EN 60715 (35 mm) or screw fixing with fixing brackets

ZB4-101-GF1 (accessories)

Dimensions (w x d x h)

mm 35 x 90 x 74

35

x 90 x 109

Weight

kg

0.12

0.15

Terminal capacity

Solid

mm

2

0.5…1.5

0.5…1.5

Flexible with ferrule

mm

2

0.5…1.5

0.5…1.5

Solid or stranded

AWG 22…16

22…16

Flat-blade screwdriver

mm 3.5 x 0.8

3.5

x 0.8

Max. tightening torque

Nm 0.6

0.6

Ambient climatic conditions

Ambient temperature Operation

°C

-25 -

+55

-25 -

+55

Storage

°C

-25 -

+70

-25 -

+70

Condensation

Prevent condensation by means of suitable measures

Relative humidity, non-condensing (IEC/EN 60068-2-30)

% 5 - 95

5 - 95

Air pressure (in operation)

hPa

795 - 1080

795 - 1080

Ambient mechanical conditions

Protection type (IEC/EN 60529, EN50178, VBG 4)

IP20

IP20

Pollution degree

2

2

Mounting position

Vertical

Vertical

Electromagnetic compatibility (EMC)

Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)

Air discharge

kV

8

8

Contact discharge

kV

Electromagnetic fields (IEC/EN 61000-4-3, RFI)

V/m

10

10

Radio interference suppression (EN 55011, EN 55022)

Class A

Class A

Burst pulses (IEC/EN 61000-4-4, level 3)

Supply cables

kV

2

2

Signal cables

kV

2

power pulses (surge) (IEC/EN 61000-4-5, level 2)

kV

0.5 (

supply cables, symmetrical)

Emitted RFI (IEC/EN 61000-4-6)

V

10

10

Insulation resistance

Clearances and creepage distances

EN 50178, EN 60947-1, UL 508, CSA C22.2 No 142

Insulation resistance

EN 50178, EN 60947-1

Supply voltage, gateway electronics and SmartWire station

electronics U

gateway

Rated operational voltage U

gateway

V DC –

24, -15 %,

+20 %

Permissible range

Supply from gateway or power

module

20.4...28.8

Ripple

% –

≦ 5

Maximum gateway current consumption at 24 V DC

mA

500 (

normally 100 coupling unit +

normally 25 per SmartWire card)

Voltage dips (IEC/EN 61131-2)

ms

10

Heat dissipation at 24 V DC

W –

Normally 6

Protection against polarity reversal

Yes

Short-circuit protection, SmartWire side

Yes

Power supply

U

AUX

(

power supply for switching the

SmartWire slaves, e.g. contactor coils)

Rated operational voltage U

AUX

V DC –

24, -15 %,

+20 % (Derating from> 40 °C)

Permissible range

V DC –

20.4…28.8,

at 45 °C: 21…28.8,

at 50 °C: 21.6…28.8,

at 55 °C: 22.2…27.6

Input current U

AUX

at 24 V DC

A

Normally 3

Ripple

% –

≦ 5

Voltage dips (IEC/EN 61131-2)

ms

10

Protection against polarity reversal

Yes

Voltage

U

s

V

Yes

Short-circuit protection, SmartWire side

No, external 3 A fuse or FAZ-Z3

SWIRE-…