HAVELLS

Miniature Circuit Breakers (MCBs)

Ambient Temperature

Compensation/Diversity Factor Chart

Maximum Permissible Rated Current (K, factor)

Diversity Factor (K, Factor)

Let Through Energy I2t

K

1

Graph 1

-25 -10 0 10 20 30 40 50 60

10A

6A

0.7

0.8

0.9

1.0

1.1

1.2

1.3

1.4

1.5

16-32A

40-63A

1-4A

K

Factor

Number of poles placed together with gap in between

1 2 3 4 5 6 7 8 9 10 11

0.6

0.7

0.8

0.9

1.0

Factor

K

2

Graph 2

Calculation I

n

/ MCB = K

1

x K

2

x I

n

Example

4 MCBs with I

n

= 10 A, and the amb. temp. is 50 ˚C kept with no gap in between

Solution

K1 =0.89 (from graph 1) K2 =0.78 (from graph 2)

I

n

/ pole = 0.89 x 0.78 x 10 = 6.94 A