4/11

Safety automation solutions

Preventa configurable safety controllers

Type XPS MC

Description

1

2

3

4

5

9

7

8

6

Description

Configurable safety controllers XPS MC

pp

Z

p

Front face of controllers:

1

LED display and system diagnostics.

2

Two LEDs for CANopen or Profibus

(1)

connection status.

3

SUB-D 9-pin male connector for connection on CANopen bus (

XPS MC16ZC/

MC32ZC

)

or SUB-D 9-pin female connector for connection on Profibus bus

(

XPS MC16ZP/MC32ZP

).

4

Solid-state safety output and "muting" indicator light terminals.

5

Power supply (24 V

c

)

and relay safety output terminals.

6

Control output terminals for power supply to safety inputs and safety input terminals.

7

RJ45 connector for connection on Modbus serial link.

8

RESET button (resetting of controller).

Rear face of controllers:

9

Fixing plate for mounting on rail.

Configurable safety controller XPS MC

pp

Z

p

,

with screw connectors

Illuminated display

1

2

3

4

5

9 10 11

7

8

6

LED details

LED

Colour

Status

Meaning

1

PWR Green On

Supply voltage present.

2

CNF Yellow On

In configuration mode.

Flashing Not configured, initial power-up.

3

E In Red

On

Internal error: all safety outputs deactivated.

4

E Ex Red

On

External error: all safety outputs associated

with the defective circuit are deactivated.

5

COM Green On

Controller communicating via the TER (RJ45)

connection.

6

R1, R2 Green On

Relay outputs 13/14, 23/24, 33/34 and

43/44

activated.

Flashing Fault on these outputs.

7

RUN Green Off

Hardware OK for the Profibus bus or the

CANopen bus.

On

Communicating on Profibus bus or on

CANopen bus. Normal status.

8

ERR Red

On

Communication impossible, configuration

error, damaged cabling or absence.

Bus deactivated

Off

Communicating on CANopen or Profibus bus.

Normal status.

Flashing

(

x 1)

Warning limit reached.

Flashing

(

x 2)

Control event error on CANopen bus.

Flashing

(

x 3)

Synchronisation error on CANopen bus.

9

1…16

1…32

Green On

Input circuit closed.

Flashing Error detected on input relating to LED.

10

o1…o6 Green On

Solid-state output activated.

Flashing Short-circuit, fault on output.

11

RUN Green On

Run mode.

Flashing Changing from run mode to stop mode.

(1)

Depending on controller model.

1

2

3

4

5

6

7

8

9