Presentation,

description

Presentation

Counting functions are required for counting parts or events, grouping objects,

incoming or outgoing flow control, and measuring the lengths or positions of items.

Premium PLCs perform these functions using

TSX CTY 2A

/

4

A

counter modules

which have a counting frequency of 40 kHz maximum. In a Premium PLC

configuration, the number of TSX CTY counter modules must be added to that of the

other application-specific modules (communication, motion control and weighing).

(

See pages 1/10 and 1/19). They are hot-swappable. Counter modules are

characterized by their number of channels:

b

2

channels with downcounting, upcounting and up/down counting for the

TSX CTY 2A

module

b

4

channels with downcounting, upcounting and up/down counting for the

TSX CTY 4A

module

The parameters of these functions are set by software configuration. The modules

take 5 V

c

or 10 to 30 V

c

sensors with solid state outputs (incremental encoders,

proximity sensors, photoelectric detectors) and with mechanical contact outputs (in

this case the counting frequency is limited to 100 Hz).

Description

The front panel of

TSX CTY 2A

(2-

channel) and

TSX CTY 4A

(4-

channel) counter

modules comprises:

1

One 15-way SUB-D connector per channel for connecting:

v

Counter sensors or incremental encoder

v

Sensor power supply

v

Encoder power supply feedback for checking that it is supplied correctly

2

One 20-way HE10 connector for 2 channels for connecting the following for each

channel:

v

Auxiliary inputs: preset, enable

v

Reflex outputs

v

Power supplies for auxiliary I/O and incremental encoders

3

Rigid casing, which:

v

Holds the electronic card

v

Locates and locks the module in its slot

4

Module diagnostic LEDs:

v

Module diagnostics:

-

Green RUN LED: module operating

-

Red ERR LED: internal fault, module failure

-

Red I/O LED: external fault

v

Channel diagnostics: Green CH

p

LED: channel diagnostics available

3

4

1

2

TSX CTY 2A

TSX CTY 4A

CH2

ERR

CH0 RUN

CH3 CH1

I/O

Modicon Premiumautomation

platform

TSX CTY 2A/4A counter modules

Operation: