8/37

Selection,

references

Selection of protection on the power supply primaries

Type of

mains supply

a

115

V single-phase

a

230

V single-phase

Power supply Thermal-magnetic circuit-breaker

(1)

Gg

fuse

Thermal-magnetic circuit-breaker

(2-

pole)

Gg

fuse

ASI ABLB3002

GB2

p

B07 MG24517

(2)

2

A GB2 DB06

MG24516

(2)

2

A

ASI ABLB3004

GB2

p

B08 MG24518

(2)

4

A GB2 DB07

MG17453

(2)

2

A

ASI ABLD3002

GB2

p

B07 MG24517

(2)

2

A GB2 DB06

MG24516

(2)

2

A

ASI ABLD3004

GB2

p

B08 MG24518

(2)

4

A GB2 DB07

MG17453

(2)

2

A

ASI ABLM3024

GB2

p

B07 MG24517

(2)

2

A GB2 DB06

MG17453

(2)

2

A

(1)

Single-phase protection, replace

p

by

C

; 2-

pole protection, replace

p

by

D.

(2)

UL certified circuit breaker.

References

Input voltage Secondary

Auto-protect

reset

Earth fault

detection

Reference

Weight

kg

Output

voltage

Nominal

power

Nominal

current

Single phase

(

N-L1)

or 2-phase

(

L1-L2)

a

100…240

V

- 15 %,

+ 10 %

50/60

Hz

c

30

V 72 W 2,4 A Auto

No

ASI ABLB3002

0.800

144

W 4,8 A Auto

No

ASI ABLB3004

1.300

72

W 2,4 A Auto

Yes

ASI ABLD3002

0.800

144

W 4,8 A Auto

Yes

ASI ABLD3004

1.300

c

30

V

72

W 2,4 A

Auto

No

ASI ABLM3024

1.300

c

24

V 72 W 3 A

Power supplies and transformers

Phaseo

Regulated switch mode power supplies

ASIABL

Power supplies for AS-Interface cabling system

ASI ABL

p

3002

1

2

3

4

5

6

7

8

9

10