5/102
Maximum configuration
The Fipio bus enables a maximum of 128 devices to be connected. This limit can, in
certain cases, be restricted depending on the type of bus manager processor and on
the devices which are connected on the bus. The maximum number of devices
which can be connected depends on:
b
The maximum size of memory space available for Fipio data which is:
v
94320
bytes
for Modicon Premium TSX P57 15
p
/25
p
/2823/35
p
processors
v
214528
bytes
for Modicon Premium TSX P57 45
p
/4823/554
M processors
b
The total number of bytes consumed by each device (see table below)
Product family
References
Base size
(
bytes)
Extension size
(
bytes)
Maximum number of connection points
TSX 57 1
p
TSX 57 2
p
/3
p
TSX 57 4
p
/5
p
Maximum number of Fipio devices
(1)
63
127
127
ATV 71/61
with VW3 A3 311 card
1280
62
62
62
Lexium 15
with AM0 FIP 001V000 card
1424
62
62
62
Magelis
i
PC, PC
with USB/FIP adaptor (addr. 63)
–
1
1
1
Inductel,
read/write stations XGK S130421, XGP S1304202
with VW3 A58301 card
1808
52
52
62
Modicon STB
STB NFP 2212
832, 896
or 1280
(2)
62
113, 105
or 73 126
Momentum
170
ADI
ppp
/
ADO
ppp
,
170
ADM 350 10/11,
170
ARM 370 10/390 10/30,
170
ADM 690 51,
170
ARN 120 90,
170
ARM 370 30/390 10
832
62
98
98
170
AAI 030 00/520 40,
170
AAO 120 00/921 00,
170
AEC 920 00,
170
AMM 090 00
1808
52
52
98
170
AAI 140 00
2304
40
40
92
TBX
(3)
(
legacy range)
TBX AES 200/ASS 400
(4)
1332
62
70
126
272
(2/4
channel
extension)
59
59
126
TBX AMS 620
1584
59
59
126
272
(2-
channel extens.)
(4-
channel extens.)
50
50
50
50
100
(4)
84
(4)
528
(8-
channel extens.)
44
44
63
(4)
TBX CEP 1622/CSP 1622/1625 1152
31
31
31
TBX DES
16
pp
/
DMS16
pp
/
DSS16
pp
1152
62
81
126
144
(
extension)
62
64
(5)
64
(5)
TBX DSS 1235
1152
144
(
extension)
62
72
85
(5)
TBX DSS 1025
1152
144
(
extension)
62
72
102
(5)
TBX EEP/ESP 08C22/1622 (IP 65) 1152
62
64
126
TBX SAP 10
1808
52
52
117
IP 67 I/O
TSX EEF 08D2/EEF 16D2
832
62
98
98
TSX ESF 08T22/EMF 16DT2
1808
52
52
98
Micro/PremiumAgent
with TSX FPP 10 card
1424
62
62
62
FipConnect profile
FRD C2
832
62
113
126
FRD C2P
1744
54
54
122
FSD C8
896
62
105
126
FSD C8P
1808
52
52
117
FSD M8
1040
62
90
126
FSD M8P
1952
48
48
109
FED C32
1280
62
73
126
FED C32P
2304
40
40
92
FED M32
1424
62
66
126
FED M32P
2448
38
38
87
Not applicable
(1)
Address 63 is reserved for the programming and diagnostic terminal.
(2)
Depending on the island's number of I/O modules (1
…32).
(3)
Discrete and analog base units must not be mixed on the same Fipio connection point.
(4)
The number of analog channels for
TBX AES/ASS/AMS
base units is limited to 1008.
(5)
The number of discrete channels for
TBX DES/DMS/DSS
base units is limited to 2048.
Maximum configuration
Presentation:
page 5/100
Description:
page 5/101
References:
page 5/103
Modicon Premium automation
platform
Fipio bus manager function
2
1
3
4
5
6
7
8
9
10