D-103
Additional information
Maintenance
Correctivemaintenance
General
General recommendations
bb
Before any intervention on the connections, switch off the cubicle, remove the
protective screens and the partitioning sheets and boxes.
bb
When reassembling the connections:
bb
use new screws, washers, nuts of the same type (class 8.8)
bb
tighten to the defined torque (refer to the tightening torque table in chapter
"Connection/Connection of power cables")
bb
apply varnish.
Hot point
Screwed connection
bb
Identify the cause: generally a loosening connection.
bb
Dismantle the assembly.
bb
Clean and rub down surfaces in contact (e.g. sandpaper N° 400).
bb
Set the connection up.
Maintenance after a fault has occured
The high currents resulting from a fault cause damage to structures, components,
busbars and cables.
Following a fault, contact your local Schneider Electric office.
Troubleshooting and interventions
For any interventions other than those described in this manual,
contact your local
Schneider Electric agency.