Connecting to terminal extension bars

bb

Check that the circuit and switchgear identification indications match.

bb

When connections are made to terminal extensions made up of several bars for

each phase, position the lugs opposite one another and insert copper spacers

between the bars.

bb

Comply with the minimum required electrical clearances between phases

of 14 mm (conforming with IEC 60439-1).

bb

Mark all nuts and the terminal extension bars with a dot of varnish after tightening

to the defined torque.

bb

Remove the top cross-member of the cubicle to simplify connection of the cables

to the bars.

bb

Tie cables of the same phase together.

Connection directly to device terminals

bb

When connections are made directly to the switchgear terminals, comply with the

tightening torque recommended by the device manufacturer.

bb

Check that the length of the screws delivered with the switchgear is compatible

with the lug thickness.

bb

Comply with the safety clearances around the switchgear devices, defined

by the manufacturer to ensure correct operation.

bb

Refit the interphase barriers and terminal shields if applicable after connection

the power cables.

bb

For the special case of connection with armoured cable, please consult us.

Removable upper cross-member.

Connection of power cables