D-101

Additional information

Maintenance

Preventive maintenance

Frequency

bb

The frequency of preventive maintenance depends primarily on the operating

conditions of the electrical switchboard.

bb

For operating conditions found in normal environments, the frequency should be

as indicated in the recommended calendar.

bb

It may be extended if the switchboard is used in a particularly clean environment

and not in an intensive manner.

bb

It must be reduced if the switchboard is used in a particularly aggressive

environment (dust, humidity, corrosive vapours, heat) or is used intensively.

Recommended calendar

Type

Action

Frequency

General inspection

Visual checks and general

cleaning.

Visual check of busbars.

Running tests

Once a year

Maintenance on functional units Inspection of the connections Every 5 years

Maintenance of ventilation

system

Cleaning of filters

Every 6 months

Maintenance of devices

According to the respective handbooks

General recommendations

Before any intervention on the connections, switch off the functional unit, remove the

protective screens and the partitioning sheets and boxes.

bb

For interventions on the connections, refer to chapter "Connections", profession

Install.

bb

When reassembling the connections:

v

use new screws, washers, nuts of the same type (class 8.8)

v

tighten to the defined torque (refer to the tightening torques table in the chapter

"Connection/Tools required")

v

apply varnish.

Method of inspection of the electrical connections

bb

Connections by lugs or screwed bars: presence of varnish, colour changes of a

copper bar.

bb

Connections by cage type terminals: if necessary, re-screw to the torque defined

by the manufacturer to compensate for a possible creep.

Please ensure that you consult the "General" chapter section dealing with

safety instructions.