A-40

Functions and

characteristics

Motor protection

MA and Micrologic 1.3-M

instantaneous trip units

MAmagnetic trip units

Circuit breakers with an MA trip unit are combined with a thermal relay and a

contactor or a starter.

Protection

……………………………………………

Magnetic protection (Im)

Short-circuit protection with an ad

j

ustable pick-up Im that initiates instantaneous

tripping if exceeded.

Im

b

= In x ... is set on an ad

j

ustment dial in multiples of the rating:

6 to 14 x In (2.5 to 100 A ratings)

v

9 to 14 x In (150 to 200 A ratings)

v

Protection version

3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D).

b

Micrologic 1.3-M trip units

Circuit breakers with a Micrologic 1.3-M trip unit are combined with a thermal relay

and a contactor.

Protection

..............................................................

Settings are made using a dial.

Short-circuits: Short-time protection (Isd)

Protection with an ad

j

ustable pick-up Isd. There is a very short delay to let through

motor starting currents.

Isd is set in amperes from 5 to 13 x In, as follows:

b

from 1600 to 4160 A for the 320 A rating.

v

from 2500 to 6500 A for the 500 A rating.

v

Short-circuits: Non-adjustable instantaneous protection (li)

Instantaneous protection with non-ad

j

ustable pick-up Ii.

Protection version

3-pole (3P 3D): 3-pole frame (3P) equipped with detection on all 3 poles (3D).

b

Indications

…………………………………………

Front indications

*UHHQ ³5HDG\´ /(' ÀDVKHV VORZO\ ZKHQ WKH FLUFXLW EUHDNHU LV UHDG\ WR WULS LQ WKH

b

event of a fault.

MAmagnetic trip units are used in

3-device

motor-feeder solutions

. They can be

mounted on all Compact NSX100/160/250

circuit breakers with performance levels

B/F/H/N/S/L.

They provide short-circuit protection for

motors up to 110 kW at 400 V.

Micrologic 1.3-M trip units are used in

3-

device motor-feeder solutions

on

Compact NSX400/630 circuit breakers with

performance levels B/F/H/N/S/L.

They provide short-circuit protection for

motors up to 250 kW at 400 V.

7KH\ DOVR SURYLGH WKH EHQH¿WV RI HOHFWURQLF

technology:

b

accurate settings

b

tests

b

"Ready" LED.

Note:

all the trip units have a transparent lead-sealable cover

that protects access to the adjustment dials.

DB112110

50

A

DB112106

559E1500.indd

version: 1.0