A-46

Functions and

characteristics

Motor protection

Micrologic 6 E-M electronic trip units

(cont.)

Micrologic 6 E-M provides Power Meter

functions with energy metering. With the

FDM121 display unit, all metering data and

operating indicators are available on the

switchboard front panel. This version also

displays the thermal image of the motor.

Power Meter functions

The built-in Power Meter functions of the Micrologic 6 E-M are the same as those for

the Micrologic 6-E presented in the section on distribution

(see page A-20)

. When

used exclusively in the three-phase version, neutral measurements are excluded.

Operating-assistance functions

The operating-assistance functions of the Micrologic 6 E-M are the same as those

for the Micrologic 6-E presented in the section on distribution

(see page A-22)

.

Special functions for motor feeders

$GGLWLRQDO RSHUDWLQJ IXQFWLRQV VSHFL¿FDOO\ IRU PRWRU IHHGHUV DUH DYDLODEOH

Phase sequence

The order in which the phases L1, L2, L3 are connected determines the direction of

motor rotation. If two phases are inverted, the direction is reversed.

Information on the direction of rotation is provided. It can be linked to an alarm to

detect an inversion in the direction following servicing on the supply under de-

energised conditions and disable restarting.

Thermal image of the rotor and stator

Micrologic 6 E-M offers a thermal-image function.

Taking into account the Ir setting and the class, an algorithm simulates rotor and

stator temperature rise. It includes the slow temperature rise of the stator and its

metal mass. Also included is the faster temperature rise of the copper rotor.

The thermal protection function trips the circuit breaker when the calculated thermal

image reaches 100 % of the permissible temperature rise.

The communication indicates the thermal-image value as a percentage of the

permissible temperature rise. One or more alarms may be assigned to selected

thresholds. A red LED on the front signals when the value exceeds 95 %.

An SDx module with two outputs programmed for thermal-image values can be used

to implement other alarm functions.

PB103365

Micrologic 6 E-M.

DB111404

E

S

C

I

1

I

2

I

3

I

165 A

100 120

%

165 A

100 120

%

164A

100 120

%

DB111405

E

S

C

°

m

otor = 9

7

%

Current values.

Thermal-image alarm.

DB111403

PC screen with motor thermal image and value monitoring.

The additional technical characteristics are identical to those of Micrologic 6-E

(see pages A-21

and A-23)

.

559E1500.indd