Protection of industrial control panels

Compact NSX circuit breakers are also

used in industrial control panels.

They serve as an incoming devices or can

be combined with contactors to protect

motor feeders:

b

compliance with worldwide standards

including IEC 60947-2 and UL 508 / CSA

22-2 no. 14

b

overload and short-circuit protection

b

isolation with positive contact indication,

making it possible to service machines

safely by isolating them from all power

sources

b

installation in universal and functional

type enclosures

b

NA switch-disconnector version.

Industrial control panels

Compact NSX circuit breakers equipped for public distribution or motor protection

functions as described in the previous pages can be used in industrial control panels.

The accessories for the Compact NSX range are suitable for the special needs of

these switchboards.

$X[LOLDULHV

All auxiliaries can be added to the circuit breaker by the user:

padlocking devices (in the OFF position)

b

rotary handle

b

status-indication auxiliary contacts (ON, OFF and tripped)

b

shunt (MX) or undervoltage (MN) releases

b

early-make or early-break contacts.

b

5RWDU\ KDQGOH

Direct or extended versions for mounting up to 600 mm behind the front:

black front with black handle

b

yellow front with red handle (for machine tools or emergency off as per IEC 204 /

b

VDE 0013).

All rotary handles can be padlocked in the OFF position. Optional door interlock,

recommended for MCC panels (motor control centres).

When the device is equipped with an extended rotary handle, a control accessory

mounted on the shaft makes it possible to operate the device with the door open.

The device can be padlocked in the OFF position in compliance with UL508.

(DUO\ PDNH RU HDUO\ EUHDN FRQWDFWV

These contacts can be used respectively to supply an MN undervoltage release

before the circuit breaker closes or to open the contactor control circuit before the

circuit breaker opens.

Special functions

Indication of thermal overloads with the SDx module.

b

Early opening of the contactor for overload faults with the SDTAM module.

b

Links with PLCs via the communication system.

b

Measurement of all electrical parameters with Micrologic A and E.

b

Programmable alarms with Micrologic 5 and 6.

b

Installation in enclosures

Compact circuit breakers can be installed in a metal enclosure together with other

devices (contactors, motor-protection circuit breakers, LEDs, etc.)

(see page A-90)

.

Compliance with North American

industrial control equipment standards

Compact NSX devices have received UL508 / CSA 22-2 no. 14 approval for

industrial control equipment of the "Manual Motor Controller", "Across the Line

Starter", "General Use" and "Disconnecting Means" types.

Type NA devices are switch-disconnectors that must always be protected upstream.

UL508 approval

&LUFXLW EUHDNHUV

Trip units

Approvals

Compact NSX100 to 630

F/N/H

TMD, Micrologic 2, 5 and 6

General Use

Motor Disconnecting Means

NA, MA, Micrologic 1.3 M, 2.2 M,

2.3 M, Micrologic 6.2 E-M and

6.3 E-M

Manual Motor Controller

Across the Line Starter

Motor Disconnecting Means

7DEOH RI SKDVH PRWRU UDWLQJV LQ KS KS

N:

V AC ratings

115

230

460

575

TMD

Micrologic 2, 5

and 6

NA, MA

Micrologic 1.3 M, 2.2 M,

2.3 M

Micrologic 6.2 E-M and

6.3 E-M

25

25

3

7.5

15

20

50

50

7.5

15

30

40

100

100

15

30

75

100

160

150

25

50

100

150

250

220

40

75

150

200

400

320

-

125

250

300

550

500

-

150

350

500

The deratings indicated on

pages B-8

and

B-9

apply to TMD, Micrologic 2, 5 and 6 trip units,

rated at 40 °C.