16 Hz 2/3 network protection

Micrologic 5 A-Z trip unit

Compact NSX circuit breakers may be used

on 16 Hz 2/3 systems with special thermal-

magnetic and electronic (Micrologic 5 A-Z)

trip units.

+] QHWZRUNV

Single-phase distribution networks with a frequency of 16 Hz 2/3 are used for

railroad applications in certain European countries.

%UHDNLQJ FDSDFLW\ IRU +] DW

9

Compact NSX circuit breakers of the 3P 2D or the 3P 3D type protect 16 Hz 2/3

networks at 250 V or 500 V.

They can be equipped with either:

a

b

TM-D thermal-magnetic trip unit for Compact NSX100 to 250

or an electronic Micrologic 5.2 A-Z trip unit for Compact NSX100 to 250 or

b

a 5.3 A-Z for Compact NSX400/630.

The possible breaking-capacity performance levels are B, F, N and H as indicated

below.

%UHDNLQJ FDSDFLW\ ,FX

Operating voltage

TMD and Micrologic 5 A-Z trip units

Performance

B

F

N

H

250 V / 500 V

Icu (kA)

25

36

50

70

Protection

TM-D thermal-magnetic trip units

Trip-unit selection

Rating

16 88

100

160

250

400

630

Compact

NSX100

TM-D

NSX160

TM-D

NSX250

TM-D

NSX100 to 250

Micrologic 5.2 A-Z

NSX400/630

Micrologic 5.3 A-Z

:LULQJ IRU 16; WR $

DB112046

DB112153

The 16 Hz 2/3 frequency does not modify the thermal settings with respect to those

at 50 Hz

(see page A-15)

7KH PDJQHWLF SLFN XSV DUH PRGL¿HG DV VKRZQ EHORZ

Magnetic

SURWHFWLRQ IRU &RPSDFW 16;

DW +] DQG DW +]

Rating (A) In at 40 °C

16 25 32 40 50 63 80 100 125 160 200 250

Pick-up (A)

Im

accur. ±20% Fixed

Ad

j

ustable

NSX100

50Hz

190 300 400 500 500 500 640 800

16Hz 2/3 170 270 360 450 450 450 580 720

NSX160/250 50Hz

190 300 400 500 500 500 640 800 1250 1250 5 to 10 In

16 Hz 2/3 170 270 360 450 450 450 580 720 1100 1100 4.5 to 9 In

Micrologic 5 A-Z trip units

Micrologic 5.2 A-Z and 5.3 A-Z are dedicated to 16 Hz 2/3 networks.

They use a suitable sampling frequency. The protection settings are identical to

those of Micrologic 5 A

(see page A-19)

. They also offer a current-measurement

IXQFWLRQ IRU WKLV VSHFL¿F IUHTXHQF\

Phase and isolated neutral interrupted- 250 / 500 V

2 poles in series - Earthed neutral - 250 / 500 V

B and F (3P 2D version)

N and H (3P 3D version)

B and F (3P 2D version)

N and H (3P 3D version)

DB115575

L

N

lo

a

d

DB115576

L

N

lo

a

d

DB115577

L

N

lo

a

d

DB115578

L

N

lo

a

d

Remark. For an operating voltage > 250 V, the installation must be

designed to eliminate all risk of double earth faults.