A-57

Switch-disconnector functions

Compact NSX100 to 630 NA switch-

GLVFRQQHFWRUV DUH DYDLODEOH LQ ¿[HG SOXJ LQ

and withdrawable versions. They use the

same accessories and offer the same

connection possibilities as the circuit-

breaker versions.

They may be interlocked with another

Compact switch-disconnector or circuit

breaker to forma source-changeover system.

Suitability for isolation with positive contact

indication

&RPSDFW 16; VZLWFK GLVFRQQHFWRUV DUH VXLWDEOH IRU LVRODWLRQ DV GH¿QHG E\ VWDQGDUG

IEC 60947-3. The corresponding conformity tests guarantee:

the mechanical reliability of the position indication, i.e. the O (OFF) position

b

LQGLFDWHG E\ WKH FRQWURO GHYLFH DOZD\V UHÀHFWV WKH RSHQ SRVLWLRQ RI WKH FRQWDFWV

the required distance between contacts is provided

v

padlocks may not be installed unless the contacts are open

v

the absence of leakage currents

b

overvoltage withstand capacity between upstream and downstream connections.

b

Installation of a rotary handle or a motor mechanism does not alter the reliability of

the position-indication system.

Emergency-off function

ACompact NSX NA is combined with an MN or MX release connected to an

emergency-off button. In an emergency, an operator at a remote location can

interrupt the circuit at rated load to isolate the entire switchboard and the

downstream loads.

Motor mechanism

Compact NSX NA devices equipped with a motor mechanism module enable remote

closing and opening. This function may be combined with the emergency-off

function. In this case, the emergency off function is combined with a closing lock-out

that must be intentionally reset (electrical diagram with closing lock-out).

Earth-leakage protection

A Vigi module may be added to a switch-disconnector to monitor all leakage currents

in the outgoing circuits of the switchboard on which the switch-disconnector is

installed. When the Vigi module detects an earth-leakage current, the switch-

disconnector interrupts the load current. This function may be combined with the

motor mechanism and the emergency-off function using an MN or MX release.

Switch-disconnector protection

The switch-disconnector can make and break its rated current. For an overload or a

short-circuit, it must be protected by an upstream device, in compliance with

installation standards.

The circuit-breaker/switch-disconnector coordination tables determine the required

upstream circuit breaker. However, due to their high-set magnetic release, Compact

NSX100 to 630 A switch-disconnectors are self-protected.

Switch-disconnector utilisation category

Depending on the rated operational current and the mechanical durability (A for

IUHTXHQW RSHUDWLRQ RU % IRU LQIUHTXHQW RSHUDWLRQ VWDQGDUG ,(&

GH¿QHV WKH

utilisation categories as shown in the table below. Compact NSX NA switch-

disconnectors comply with utilisation categories AC22A or AC23A.

PB103199-28

Compact NSX switch-disconnector.

PB103372-34

Compact NSX switch-disconnector

equipped with a motor mechanism module.

PB103629-31

Compact NSX switch-disconnector

equipped with a Vigi module.

Utilisation category

Typical applications

Infrequent

operation

Frequent

operation

AC-21A

AC-21B

Resistive loads including moderate overloads (cos

K

=

0.95)

AC-22A

AC-22B

Mixed resistive and inductive loads including moderate

overloads (cos

K

= 0.65)

AC-23A

AC-23B

Motor loads or other highly inductive loads (cos

K

= 0.45

or 0.35)