A-63

By combining a remote-operated source-

changeover system with an integrated BA or

8$ DXWRPDWLF FRQWUROOHU LW LV SRVVLEOH WR

automatically control source transfer

according to user-selected sequences.

PB100855-30

BA controller.

PB100856-30

UA controller.

PB100857-35

$X[LOLDU\ FRQWURO SODWH IRU D %$ RU 8$ FRQWUROOHU

Functions of the BA and UA controllers

Controller

BA

UA

Compatible circuit breakers

Compact NSX100 to 630

circuit breakers

4-position switch

Automatic operation

b

b

Forced operation on Normal source

b

b

Forced operation on Replacement source

b

b

Stop (both Normal and Replacement sources OFF)

b

b

Automatic operation

Monitoring of the Normal source and automatic transfer from one

source to the other

b

b

Engine generator set start-up control

b

Delayed shutdown (ad

j

ustable) of engine generator set

b

Load shedding and reconnection of non-priority loads

b

Transfer to Replacement source if one of the Normal source phases

is absent

b

Test

By opening the P25M circuit breaker upstream of the controller

b

By pressing the test button on the front of the controller

b

Indications

Circuit-breaker status indication on the front of the controller: ON,

OFF, fault trip

b

b

Automatic-mode indication contact

b

b

Other functions

Selection of type of Normal source

(single-phase or three-phase)

b

Voluntary transfer to Replacement source

b

b

Forced operation on Normal source if Replacement source is not

operational

b

Additional test contact (not part of controller)

Transfer to Replacement source only if contact closed (e.g. for a UR

frequency check)

b

b

Setting of maximum start-up time for the Replacement-source

b

Power supply

Control voltages

(1)

220 to 240 V 50/60 Hz

b

b

380 to 415 V 50/60 Hz

b

b

440 V 60 Hz

b

b

Operating thresholds

Undervoltage

0.35 Un

y

voltage

y

0.7 Un

b

b

Phase failure

0.5 Un

y

voltage

y

0.7 Un

b

Voltage presence

voltage

u

0.85 Un

b

b

Characteristics of output contacts (dry, volt-free contacts)

Rated thermal current (A)

8

Minimum load

10 mA at 12 V

AC

DC

Utilisation category (IEC 60947-5-1)

AC12 AC13 AC14 AC15 DC12 DC13

Operational current (A) 24 V

8

7

5

6

8

2

48 V

8

7

5

5

2

-

110 V

8

6

4

4

0.6

-

220/240 V

8

6

4

3

-

-

250 V

-

-

-

-

0.4

-

380/415 V

5

-

-

-

-

-

440 V

4

-

-

-

-

-

660/690 V

-

-

-

-

-

-

(1)

7KH FRQWUROOHU LV SRZHUHG E\ WKH $&3 DX[LOLDULHV FRQWURO SODWH 7KH VDPH YROWDJH PXVW

EH XVHG IRU WKH $&3 SODWH WKH ,9( XQLW DQG WKH FLUFXLW EUHDNHU RSHUDWLQJ PHFKDQLVPV ,I WKLV

YROWDJH LV WKH VDPH DV WKH VRXUFH YROWDJH WKHQ WKH ³1RUPDO´ DQG ³5HSODFHPHQW´ VRXUFHV FDQ

EH XVHG GLUHFWO\ IRU WKH SRZHU VXSSO\ ,I QRW DQ LVRODWLRQ WUDQVIRUPHU PXVW EH XVHG

559E1700.indd