A-62

Functions and

characteristics

Source-changeover systems

Remote-operated and automatic source-

changeover systems

Coupling accessory on base plate

Remote-operated systems

It is made up of two devices with motor mechanisms, mounted on a base plate and

combined with:

an electrical interlocking unit

b

optional mechanical interlocking system.

b

Electrical interlocking unit (IVE)

Interlocks two devices equipped with motor mechanisms and auxiliary contacts.

The IVE unit is mandatory to ensure the necessary time-delays required for safe

switching.

Mechanical interlocking system

The mechanical interlocking system is strongly recommended to limit the effects of

design or wiring errors and to avoid manual switching errors.

Automatic systems

An automatic controller can manage switching from one source to the other.

The controller can be:

a device provided by the customer

b

an integrated BA controller

b

an integrated UA controller.

b

An integrated BA or UA automatic controller manages source transfer according to

user-selected sequences that can include source priorities, start-up of a generator,

return to the Normal source, etc. An ACP auxiliaries control plate facilitates

installation of the BA and UA controllers. The plate includes two circuit breakers to

protect the control circuits and two contactors to control the motor mechanisms of

the devices.

Coupling accessory on base plate

This accessory may be used with a manual or remote-operated source-changeover

system (with or without an automatic controller). It respects the mounting distance

between the devices secured to the ACP plate and provides downstream coupling of

the two sets of busbars. It is compatible with standard device accessories.

The short terminal shields of the device can be installed on the upstream connectors

of the coupling accessory. Downstream, it is possible to use the connection

accessories and the long or short terminal shields of the device.

PB103832-51

Remote-operated source-changeover system.

DB112197

Q

N

Ø5...8

Ø5...8

1

2

3

5

4

1

Circuit breaker QN equipped with a motor mechanism and

DX[LOLDU\ FRQWDFWV FRQQHFWHG WR WKH 1RUPDO VRXUFH

2

Circuit breaker QR equipped with a motor mechanism and

DX[LOLDU\ FRQWDFWV FRQQHFWHG WR WKH 5HSODFHPHQW VRXUFH

3

Base plate with mechanical interlocking

4

Electrical interlocking unit IVE

5

&RXSOLQJ DFFHVVRU\ GRZQVWUHDP FRQQHFWLRQ

DB112199

1

2

3

4

Standard device accessories may be used for the coupling

accessory on the base plate.

1

Short terminal shields

2

Terminals

3

Interphase barriers

4

Long terminal shields

559E1700.indd

version: 1.0