PB103366

Micrologic TM-D trip unit.

Functions and

characteristics

Special applications

Protection of 400 Hz systems

Compact NSX circuit breakers may be used

on 400 Hz systems.

+] GLVWULEXWLRQ V\VWHPV

The main 400 Hz applications are in aeronautics and certain military ships. Modern

aircraft have three-phase 115/200 V 400 Hz networks.

Impact on protective devices

Due to the higher frequency, circuit breakers are sub

j

ected to additional temperature

rise for identical current levels, resulting from higher losses caused by Foucault

currents and an increase in the skin effect (reduction in the useful CSA of

conductors). To remain within the rated temperature-rise limits of devices, current

derating is required.

The power levels of 400 Hz applications rarely exceed a few hundred kW with

relatively low short-circuit currents, generally not exceeding four times the rated

current.

The standard Compact NSX and Masterpact NT/NW ranges are suitable for 400 Hz

DSSOLFDWLRQV LI GHUDWLQJ FRHI¿FLHQWV DUH DSSOLHG WR WKH SURWHFWLRQ VHWWLQJV 6HH WKH

derating table below.

%UHDNLQJ FDSDFLW\ RI &RPSDFW 16; FLUFXLW EUHDNHUV

LQ +] 9 V\VWHPV

&LUFXLW EUHDNHU

%UHDNLQJ FDSDFLW\ ,FX

NSX100

10 kA

NSX160

10 kA

NSX250

10 kA

NSX400

10 kA

NSX630

10 kA

Trip units equipped with thermal-magnetic

protection

The 400 Hz current settings are obtained by multiplying the 50 Hz values by the

IROORZLQJ DGDSWDWLRQ FRHI¿FLHQW

K1 for thermal trip units

b

K2 for magnetic trip units.

b

7KHVH FRHI¿FLHQWV DUH LQGHSHQGHQW RI WKH WULS XQLW VHWWLQJ

Thermal trip units

The current settings are lower at 400 Hz than at 50 Hz (K1 < 1).

Magnetic trip units

The current settings are conversely higher at 400 Hz than at 50 Hz (K2 > 1).

Consequently, when the trip units are ad

j

ustable, they must be set to the minimum

value.

$GDSWDWLRQ FRHI¿FLHQWV IRU WKHUPDO PDJQHWLF WULS XQLWV

Circuit

EUHDNHU

Trip unit

In (A)

50Hz

Thermal at 40°C Im (A)

50Hz

Magnetic

K1

400 Hz

K2

400 Hz

NSX100

TM16G

16

0.95

15

63

1.6

100

TM25G

25

0.95

24

80

1.6

130

TM40G

40

0.95

38

80

1.6

130

TM63G

63

0.95

60

125

1.6

200

NSX100 TM16D

16

0.95

15

240

1.6

300

TM25D

25

0.95

24

300

1.6

480

TM40D

40

0.95

38

500

1.6

800

TM63D

63

0.95

60

500

1.6

800

TM80D

80

0.9

72

650

1.6

900

TM100D

100

0.9

90

800

1.6

900

NSX250 TM100D 100 0.9

90

800

1.6

900

TM160D 160 0.9

144

1250

1.6

2000

TM200D 200 0.9

180

1000 to 2000 1.6

1600 to

3200

TM250D 250 0.9

225

1250 to 2500 1.6

2000 to

4000

Example

NSX100 equipped with a TM16G with 50 Hz settings Ir = 16 A and Im = 63 A.

400 Hz settings Ir = 16 x 0.95 = 15 A and Im = 63 A x 1.6 = 100 A.

A-52