A-45

Micrologic 6.2 / 6.3 E-M

Ratings (A)

In at 65 °C

(1)

25 50 80 150 220 320 500

Circuit breaker

Compact NSX100

b b b

-

-

-

-

Compact NSX160

b b b b

-

-

-

Compact NSX250

b b b b b

-

-

Compact NSX400

-

-

-

-

-

b

-

Compact NSX630

-

-

-

-

-

b b

L

Overloads: Long-time protection

Pick-up (A)

Ir

Dial setting

Value depending on trip-unit rating (In) and setting on dial

Tripping between

1.05 and 1.20 Ir

In = 25 A Ir = 12 14

16

18

20

22

23

24

25

In = 50 A Ir = 25 30

32

36

40

42

45

47

50

In = 80 A Ir = 35 42

47

52

57

60

65

72

80

In = 150 A Ir = 70 80

90

100 110 120 130 140 150

In = 220 A Ir = 100 120 140 155 170 185 200 210 220

In = 320 A Ir = 160 180 200 220 240 260 280 300 320

In = 500 A Ir = 250 280 320 350 380 400 440 470 500

Keypad setting

)LQH DGMXVWPHQWV LQ $ VWHSV EHORZ PD[LPXP YDOXH GH¿QHG E\ GLDO VHWWLQJ

Trip class as per IEC 60947-4-1

5

10

20

30

Time delay (s)

tr

1.5 x Ir 120

240 480 720 for warm motor

depending on selected trip class

6 x Ir

6.5

13.5 26

38 for cold motor

7.2 x Ir 5

10

20

30 for cold motor

Thermal memory

20 minutes before and after tripping

Cooling fan

Settings for self-cooled or fan-cooled motors

S

0

6KRUW FLUFXLWV 6KRUW WLPH SURWHFWLRQ ZLWK ¿[HG WLPH GHOD\

Pick-up (A)

accuracy ±15 %

Isd

= Ir x ...

5

6

7

8

9

10

11

12

13

Time delay (ms)

tsd

non-ad

j

ustable

Non-tripping time

20

Maximum break time

60

I

Short-circuits: Non-adjustable instantaneous protection

Pick-up (A)

accuracy ±15 %

Ii

non-ad

j

ustable

425 750 1200 2250 3300 4800 6500

Non-tripping time

Maximum break time

0 ms

30 ms

G

Ground faults

Pick-up (A)

accuracy ±10 %

Ig

= In x ...

Dial setting

In = 25 A Ig = 0.6 0.6 0.6 0.6 0.7 0.8 0.9 1

Off

In = 50 A Ig = 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

Off

In > 50 A Ig = 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1

Off

¿QH DGMXVWPHQWV LQ [ ,Q VWHSV

Time delay (ms)

tg

0

0.1 0.2 0.3 0.4

Non-tripping time

20 80

140 230 350

Maximum break time

80 140 200 320 500

Phase unbalance or phase loss

Pick-up (A)

accuracy ±20 %

lunbal

= in % average current

(2)

ad

j

ustable from 10 to 40 %, default setting = 30 %

¿QH DGMXVWPHQWV LQ VWHSV XVLQJ WKH NH\SDG

activated during motor starting

Time delay (s)

tunbal

0.7 s during starting

1 to 10 seconds during normal operation, default setting = 4 seconds

¿QH DGMXVWPHQWV LQ V VWHSV XVLQJ WKH NH\SDG

Locked rotor

Pick-up (A)

accuracy ±10 %

Ijam

= Ir x ...

1 x 8 Ir with Off position, default setting = Off

¿QH DGMXVWPHQWV LQ [ ,U VWHSV XVLQJ WKH NH\SDG

disabled during motor starting

Time delay (s)

tjam

=

1 to 30 seconds

¿QH DGMXVWPHQWV LQ V VWHSV XVLQJ WKH NH\SDG GHIDXOW VHWWLQJ V

Under-load (under-current)

Pick-up (A)

accuracy ±10 %

Iund

= Ir x ...

0.3 x 0.9 Ir with Off position, default setting = Off

Fine ad

j

ustments in Ir x 0.01 steps using the RSU software

activated during motor starting

Time delay (s)

tund

=

1 to 200 seconds

¿QH DGMXVWPHQWV LQ V VWHSV XVLQJ WKH 568 VRIWZDUH GHIDXOW VHWWLQJ V

Long starts

Pick-up (A)

accuracy ±10 %

Ilong

= Ir x ...

1 x 8 Ir with Off position, default setting = Off

Fine ad

j

ustments in Ir x 0.01 steps using the RSU software

activated during motor starting

Time delay (s)

tlong

=

1 to 200 seconds

¿QH DGMXVWPHQWV LQ V VWHSV XVLQJ WKH 568 VRIWZDUH GHIDXOW VHWWLQJ V

(1)

Motor standards require operation at 65 °C. Circuit-breaker ratings are derated to take this requirement into account.

(2)

The unbalance measurement takes into account the most unbalanced phase with respect to the average current.

559E1500.indd