A-44

Functions and

characteristics

Motor protection

Micrologic 6 E-M electronic trip units

Protection

……………………………………………

7KH SURWHFWLRQ IXQFWLRQV DUH LGHQWLFDO WR WKRVH RI 0LFURORJLF 0 DQG FDQ EH ¿QH

ad

j

usted via the keypad .

$FFHVV WR VHWWLQJ PRGL¿FDWLRQV YLD WKH NH\SDG LV SURWHFWHG E\ D ORFNLQJ IXQFWLRQ

that is controlled by a microswitch . The lock is activated automatically if the

keypad is not used for 5 minutes. Access to the microswitch is protected by a

transparent lead-sealable cover. It is possible to scroll through settings and

measurements with the cover closed.

Overloads (or thermal), class and short-circuits

The long-time, short-time and instantaneous functions are identical to those of

Micrologic 2-M.

In addition, there is trip class 30 for long-time protection and a setting for self-cooled

or fan-cooled motors ( ).

Ground-fault protection (Ig)

Residual type ground-fault protection with an ad

j

ustable pick-up

Ig

(with Off position)

and ad

j

ustable time delay

tg

.

Phase unbalance or phase loss (lunbal)

This function opens the circuit breaker if a phase unbalance occurs:

that is greater than the

b

Iunbal

SLFN XS WKDW FDQ EH ¿QH DGMXVWHG IURP WR

(30 % by default)

following the

b

tunbal

time delay that is:

0.7 s during starting

v

ad

j

ustable from 1 to 10 seconds (4 seconds by default) during normal operation.

v

Phase loss is an extreme case of phase unbalance and leads to tripping under the

same conditions.

Locked rotor (Ijam)

This function detects locking of the motor shaft caused by the load.

During motor starting

(see page A-43),

the function is disabled.

During normal operation, it causes tripping:

above the

b

Ijam

SLFN XS WKDW FDQ EH ¿QH DGMXVWHG IURP WR [ ,U

in con

j

unction with the

b

tjam

time delay that can be ad

j

usted from 1 to 30 seconds.

Under-load (Iund)

7KLV IXQFWLRQ GHWHFWV PRWRU QR ORDG RSHUDWLRQ GXH WR LQVXI¿FLHQW ORDG H J D GUDLQHG

pump). It detects phase undercurrent.

During motor starting

(see page A-43),

the function is always enabled.

During normal operation, it causes tripping:

below the

b

Iund

SLFN XS WKDW FDQ EH ¿QH DGMXVWHG IURP WR [ ,U

in con

j

unction with the

b

tund

time delay that can be ad

j

usted from 1 to 200

seconds.

Long starts (Ilong)

This protection supplements thermal protection (class).

It is used to better ad

j

ust protection to the starting parameters.

It detects abnormal motor starting, i.e. when the starting current remains too high or

too low with respect to a pick-up value and a time delay.

It causes tripping:

in relation with a

b

llong

SLFN XS WKDW FDQ EH ¿QH DGMXVWHG IURP WR [ ,U

in con

j

unction with the

b

tlong

time delay that can be ad

j

usted from 1 to 200

seconds.

(see "long starts" page A-43)

Display of type of fault

……………………………

On a fault trip, the type of fault (Ir, Isd, Ii, Ig, lunbal, l

j

am), the phase concerned and

the interrupted current are displayed.

Indications

…………………………………………

Front indications

*UHHQ ³5HDG\´ /(' ÀDVKHV VORZO\ ZKHQ WKH FLUFXLW EUHDNHU LV UHDG\ WR WULS LQ WKH

b

event of a fault.

Red alarm LED for motor operation: goes ON when the thermal image of the rotor

b

or stator is greater than 95% of the permissible temperature rise.

5HPRWH LQGLFDWLRQV YLD 6'7$0 RU 6'[ PRGXOH

See description on

page A-42

for SDTAM and

page A-81

for SDx.

Note:

all the trip units have a transparent lead-sealable cover

that protects access to the adjustment dials.

Micrologic 6.E-M is used in

2-device

motor-feeder solutions

.

It provides the same protection as

Micrologic 2-M:

b

short-circuits

b

overloads with selection of the same trip

classes (5, 10 or 20), plus trip class 30 for

starting of machines with high inertia.

,Q DGGLWLRQ LW RIIHUV VSHFL¿F PRWRU

protection functions that can be set via the

keypad.