Magnetic trip units

MA 2.5 to 220

Ratings (A)

In at 65 °C

(1)

2.5 6.3 12.5 25

50

100 150 220

Circuit breaker

Compact NSX100

b

b

b

b

b

b

-

-

Compact NSX160

-

-

-

b

b

b

b

-

Compact NSX250

-

-

-

-

-

b

b

b

Instantaneous magnetic protection

Pick-up (A)

accuracy ±20 %

Im

= In x ...

Ad

j

ustable from 6 to 14 x In

(settings 6, 7, 8, 9, 10, 11, 12, 13, 14)

Ad

j

ustable from 9 to 14 x In

(settings 9, 10, 11, 12, 13,

14)

Time delay (ms)

tm

¿[HG

Micrologic 1.3-M

Ratings (A)

In at 65 °C

(1)

320

500

Circuit breaker

Compact NSX400

b

-

Compact NSX630

b

b

S

Short-time protection

Pick-up (A)

accuracy ±15 %

Isd

Ad

j

ustable directly in amps

9 settings: 1600, 1920, 2440, 2560,

2880, 3200, 3520, 3840, 4160 A

9 settings: 2500, 3000, 3500, 4000,

4500, 5000, 5500, 6000, 6500 A

Time delay (ms)

tsd

Non-ad

j

ustable

Non-tripping time

Maximum break time

20

60

I

Instantaneous protection

Pick-up (A)

accuracy ±15 %

Ii

non-ad

j

ustable

4800

6500

Non-tripping time

Maximum break time

0

30 ms