A-42

Functions and

characteristics

Motor protection

Micrologic 2-M electronic trip units

Circuit breakers with a Micrologic 2.2 / 2.3-M trip unit include protection similar to an

inverse-time thermal relay. They are combined with a contactor.

Protection

..............................................................

Settings are made using a dial.

Overloads (or thermal protection): Long-time protection and trip class (Ir)

Inverse-time thermal protection against overloads with ad

j

ustable pick-up Ir.

Settings are made in amperes. The tripping curve for the long-time protection, which

indicates the time delay

tr

EHIRUH WULSSLQJ LV GH¿QHG E\ WKH VHOHFWHG WULS FODVV

Trip class (class)

The class is selected as a function of the normal motor starting time.

Class 5: starting time less than 5 s

b

Class 10: starting time less than 10 s

b

Class 20: starting time less than 20 s

b

For a given class, it is necessary to check that all motor-feeder components are

sized to carry the 7.2 Ir starting current without excessive temperature rise during the

time corresponding to the class.

Short-circuits: Short-time protection (Isd)

Protection with an ad

j

ustable pick-up

Isd

. There is a very short delay to let through

motor starting currents.

Short-circuits: Non-adjustable instantaneous protection (li)

Instantaneous protection with non-ad

j

ustable pick-up

Ii

.

Phase unbalance or phase loss (lunbal) ( )

This function opens the circuit breaker if a phase unbalance occurs:

WKDW LV JUHDWHU WKDQ WKH ¿[HG SLFN XS

b

Iunbal

following the non-ad

j

ustable time delay

b

tunbal

equal to:

0.7 s during starting

v

4 s during normal operation.

v

Phase loss is an extreme case of phase unbalance and leads to tripping under the

same conditions.

Indications

…………………………………………

Front indications

*UHHQ ³5HDG\´ /(' ÀDVKHV VORZO\ ZKHQ WKH FLUFXLW EUHDNHU LV UHDG\ WR WULS LQ WKH

b

event of a fault.

Red alarm LED for motor operation: goes ON when the thermal image of the rotor

b

and stator is greater than 95% of the permissible temperature rise.

Remote indications via SDTAM module

Compact NSX devices with a Micrologic 2 can be equipped with an SDTAM module

dedicated to motor applications for:

a contact to indicate circuit-breaker overload

b

a contact to open the contactor. In the event of a phase unbalance or overload,

b

this output is activated 400 ms before circuit-breaker tripping to open the contactor

and avoid circuit breaker tripping.

This module takes the place of the MN/MX coils and an OF contact.

Note:

all the trip units have a transparent lead-sealable cover

that protects access to the adjustment dials.

PB103376

SDTAM remote indication relay module

with its terminal block.

Micrologic 2-M trip units provide built-in

thermal and magnetic protection. They are

used in

2-device motor-feeder solutions

on Compact NSX100 to 630 circuit breakers

with performance levels B/F/H/N/S/L.

They provide protection for motors up to

315 kW at 400 V against:

b

short-circuits

b

overloads with selection of a trip class (5,

10 or 20)

b

phase unbalance.