Vigicompact NSX100 to 630 circuit breakers with
earth-leakage protection
Addition of the Vigi module does not alter circuit-breaker characteristics:
compliance with standards
b
degree of protection, class II front-face insulation
b
positive contact indication
b
electrical characteristics
b
trip-unit characteristics
b
installation and connection modes
b
indication, measurement and control auxiliaries
b
installation and connection accessories.
b
Dimensions and weights
NSX100/160/250
NSX400/630
Dimensions
3 poles
105 x 236 x 86
135 x 355 x 110
W x H x D (mm)
4 poles
140 x 236 x 86
180 x 355 x 110
Weight (kg)
3 poles
2.5
8.8
4 poles
3.2
10.8
Vigi earth-leakage protection modules
Compliance with standards
IEC 60947-2, annex B.
b
Decree dated 14 November 1988 (for France).
b
IEC 60755, class A, immunity to DC components up to 6 mA
b
operation down to -25 °C as per VDE 664.
b
Remote indications
Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal
tripping due to an earth fault.
Use of 4-pole Vigi module with a 3-pole Compact NSX
In a 3-phase installation with an uninterrupted neutral, an accessory makes it
possible to use a 4-pole Vigi module with connection of the neutral cable.
Power supply
Vigi modules are self-supplied internally by the distribution-system voltage and
therefore do not require any external source. They continue to function even when
supplied by only two phases.
Vigi module selection
DB112147
1 2
3
4 5 6 7
1
Sensitivity setting
2
Time-delay setting (for selective earth-leakage protection).
3
/HDG VHDO ¿[WXUH IRU FRQWUROOHG DFFHVV WR VHWWLQJV
4
Test button simulating an earth-fault for regular checks on
the tripping function
5
Reset button (reset required after earth-fault tripping).
6
Rating plate
7
Housing for SDV auxiliary contact.
Plug-in devices
The Vigi module can be installed on a plug-
in base. Special accessories are required
(see catalogue number chapter).
Type
Vigi ME
Vigi MH
Vigi MB
Number of poles
3, 4
(1)
3, 4
(1)
3, 4
(1)
NSX100
b
b
-
NXS160
b
b
-
NSX250
-
b
-
NSX400
-
-
b
NSX630
-
-
b
Protection characteristics
Sensitivity
¿[HG
ad
j
ustable
ad
j
ustable
I
%
n (A)
0.3
0.03 - 0.3 - 1 - 3 - 10
0.3 - 1 - 3 - 10 - 30
Time delay
¿[HG
ad
j
ustable
ad
j
ustable
Intentional delay
(ms)
< 40
0 - 60
(2)
- 150
(2)
- 310
(2)
0 - 60 - 150 - 310
Max. break time
(ms)
< 40
< 40 < 140 < 300 < 800
< 40 < 140 < 300 < 800
Rated voltage
V AC 50/60 Hz
200...440
200... 440 - 440...550
200...440 - 440...550
(1)
Vigi 3Pmodules may also be used on 3P circuit breakers used for two-phase protection.
(2)
If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.
Operating safety
The Vigi module is a user safety device. It must be tested at regular intervals (every 6
months).