Vigicompact NSX100 to 630 circuit breakers with

earth-leakage protection

Addition of the Vigi module does not alter circuit-breaker characteristics:

compliance with standards

b

degree of protection, class II front-face insulation

b

positive contact indication

b

electrical characteristics

b

trip-unit characteristics

b

installation and connection modes

b

indication, measurement and control auxiliaries

b

installation and connection accessories.

b

Dimensions and weights

NSX100/160/250

NSX400/630

Dimensions

3 poles

105 x 236 x 86

135 x 355 x 110

W x H x D (mm)

4 poles

140 x 236 x 86

180 x 355 x 110

Weight (kg)

3 poles

2.5

8.8

4 poles

3.2

10.8

Vigi earth-leakage protection modules

Compliance with standards

IEC 60947-2, annex B.

b

Decree dated 14 November 1988 (for France).

b

IEC 60755, class A, immunity to DC components up to 6 mA

b

operation down to -25 °C as per VDE 664.

b

Remote indications

Vigi modules may be equipped with an auxiliary contact (SDV) to remotely signal

tripping due to an earth fault.

Use of 4-pole Vigi module with a 3-pole Compact NSX

In a 3-phase installation with an uninterrupted neutral, an accessory makes it

possible to use a 4-pole Vigi module with connection of the neutral cable.

Power supply

Vigi modules are self-supplied internally by the distribution-system voltage and

therefore do not require any external source. They continue to function even when

supplied by only two phases.

Vigi module selection

DB112147

1 2

3

4 5 6 7

1

Sensitivity setting

2

Time-delay setting (for selective earth-leakage protection).

3

/HDG VHDO ¿[WXUH IRU FRQWUROOHG DFFHVV WR VHWWLQJV

4

Test button simulating an earth-fault for regular checks on

the tripping function

5

Reset button (reset required after earth-fault tripping).

6

Rating plate

7

Housing for SDV auxiliary contact.

Plug-in devices

The Vigi module can be installed on a plug-

in base. Special accessories are required

(see catalogue number chapter).

Type

Vigi ME

Vigi MH

Vigi MB

Number of poles

3, 4

(1)

3, 4

(1)

3, 4

(1)

NSX100

b

b

-

NXS160

b

b

-

NSX250

-

b

-

NSX400

-

-

b

NSX630

-

-

b

Protection characteristics

Sensitivity

¿[HG

ad

j

ustable

ad

j

ustable

I

%

n (A)

0.3

0.03 - 0.3 - 1 - 3 - 10

0.3 - 1 - 3 - 10 - 30

Time delay

¿[HG

ad

j

ustable

ad

j

ustable

Intentional delay

(ms)

< 40

0 - 60

(2)

- 150

(2)

- 310

(2)

0 - 60 - 150 - 310

Max. break time

(ms)

< 40

< 40 < 140 < 300 < 800

< 40 < 140 < 300 < 800

Rated voltage

V AC 50/60 Hz

200...440

200... 440 - 440...550

200...440 - 440...550

(1)

Vigi 3Pmodules may also be used on 3P circuit breakers used for two-phase protection.

(2)

If the sensitivity is set to 30 mA, there is no time delay, whatever the time-delay setting.

Operating safety

The Vigi module is a user safety device. It must be tested at regular intervals (every 6

months).