A-30
Functions and
characteristics
Compact NSX communication
RSU and RCU utilities
RSU (Remote Setting Utility)
This utility is used to set the protection functions and alarms for each Masterpact and
Compact NSX device.
After connection to the network and entry of the circuit-breaker Modbus address, the
software automatically detects the type of trip unit installed.
There are two possible operating modes.
Off-line with the software disconnected from the
communication network
For each selected circuit breaker, the user can do the following.
Determine the protection settings
The settings are carried out on a screen that shows the front of the trip unit. The
Micrologic setting dials, keypad and screen are simulated for easy use of all
Micrologic setting functions.
Save and duplicate the protection settings
(DFK FRQ¿JXUDWLRQ FUHDWHG FDQ EH VDYHG IRU VXEVHTXHQW GHYLFH SURJUDPPLQJ ,W FDQ
also be duplicated and used as the basis for programming another circuit breaker.
On-line with the software connected to the network
Similarly, for each selected circuit breaker, the user can do the following.
Display the current settings
The software displays the trip unit and provides access to all settings.
View the corresponding protection curves
A graphic curve module in the software displays the protection curve corresponding
WR WKH VHWWLQJV ,W LV SRVVLEOH WR OD\ D VHFRQG FXUYH RYHU WKH ¿UVW IRU GLVFULPLQDWLRQ
studies.
Modify settings in a secure manner
There are different levels of security:
b
password: by default, it is the same for all devices, but can be differentiated for
v
each device
locking of the Modbus interface module which must be unlocked before the
v
corresponding device can be set remotely
maximum settings limited by the positions of the two dials on the trip unit.
v
These dials, set by the user, determine the maximum settings that can be made via
the communication system.
6HWWLQJV DUH PRGL¿HG E\
b
either direct, on-line setting of the protection settings on the screen
v
or by loading the settings prepared in off-line mode. This is possible only if the
v
positions of the dials allow the new settings.
All manual settings made subsequently on the device have priority.
Program alarms
Up to 12 alarms can be linked to measurements or events.
b
WZR DODUPV DUH SUHGH¿QHG DQG DFWLYDWHG DXWRPDWLFDOO\
b
Micrologic 5: overload (Ir)
v
Micrologic 6: overload (Ir) and ground fault (Ig)
v
thresholds, priorities and time delays can be set for 10 other alarms. They may be
b
selected from a list of 91 alarms
Set the outputs of the SDx relays
7KLV LV UHTXLUHG ZKHQ WKH XVHU ZDQWV WR FKDQJH WKH VWDQGDUG FRQ¿JXUDWLRQ DQG
assign different signals to the 2 outputs of the SDx relay.
RCU (Remote Control Utility)
The RCU utility can be used to test communication for all the devices connected to
the Modbus network. It is designed for use with Compact NSX, Masterpact,
Advantys OTB and Power Meter devices. It offers a number of functions.
Mini supervisor
Display of I, U, f, P, E and THD measurements for each device, via navigation
b
Display of ON/OFF status
b
Open and close commands for each device
$ FRPPRQ RU LQGLYLGXDO SDVVZRUG PXVW ¿UVW EH HQWHUHG
When all functions have been tested, this utility is replaced by the supervision
software selected for the installation.
Two utilities, RSU and RCU, are available to
assist in starting up a communicating
installation.
They can be downloaded from the
6FKQHLGHU (OHFWULF LQWHUQHW VLWH DQG LQFOXGH
a "Live update" function that enables
immediate updating.
DB112216
DB112217
RSU: Micrologic Remote Setting Utility.
DB112215
RCU: Remote Control Utility for communication tests.
559E1300.indd
version: 1.0