All Compact NSX devices can be equipped

with the communication function via a

prewired connection system and a Modbus

network interface.

The interface can be connected directly or

via the FDM121 switchboard display unit.

Four functional levels can be combined to

adapt to all supervision requirements.

A-26

Functions and

characteristics

Compact NSX communication

Communications modules

Four functional levels

The Compact NSX can be integrated in a Modbus communication environment. Four

functional levels can be used separately or combined.

Communication of status indications

This level is compatible with all Compact NSX circuit breakers, whatever the trip unit,

and with all switch-disconnectors. Using the BSCM module, the following information

is accessible:

ON/OFF position (O/F)

b

trip indication (SD)

b

fault-trip indication (SDE).

b

Communication of commands

Also available on all circuit breakers and switch-disconnectors, this level

(communicating remote control) can be used to:

open

b

close

b

reset.

b

Communication of measurements with Micrologic 5 / 6 A or E

This level provides access to all available information:

instantaneous and demand values

b

maximeters/minimeters

b

energy metering

b

demand current and power

b

power quality.

b

Communication of operating assistance with Micrologic 5 / 6 A or E

protection and alarm settings

b

time-stamped histories and event tables

b

maintenance indicators.

b

1

Modbus network

2

Modbus interface

3

NSX cord

4

Internal terminal block for communication via NSX cord

5

BSCM module

6

Prefabricated wiring

7

Micrologic trip unit

8

FDM121 display

9

RJ45 cable

10

Line terminator (on unused connector if applicable)

Communication components and connections

Connections

Compact NSX is connected to the Modbus interface or

b

FDM121 display unit via the internal terminal block for the NSX

cord equipped with an RJ45 connector.

cord available in three lengths: 0.35 m, 1.3 m and 3 m.

v

insulated 0.35 m version for installations > 480 V AC

v

lengths up to 10 m possible using extensions.

v

The FDM121 display unit is connected to the Modbus

b

interface by a communication cable with RJ45 connectors on

both ends.

DB112060

1.

3 m

DB115568

Modbus

2

4

V

DC

10

10

559E1300.indd

version: 1.0