Functions and

characteristics

Earth-leakage protection

Add-on protection against insulation faults

using a Vigi module or Vigirex relay

There are two ways to add earth-leakage

protection to any three or four-pole Compact

NSX100 to 630 circuit breaker equipped

with a magnetic, thermal-magnetic or

Micrologic 2, 5 or 6 trip unit:

b

by adding a Vigi module to the circuit

breaker to form a Vigicompact NSX

b

by using a Vigirex relay and separate

toroids.

Circuit breaker with add-on Vigi module

(Vigicompact NSX)

For general characteristics of circuit breakers,

b

see pages A-6 and A-7

.

Add-on Vigi modules. Earth-leakage protection is achieved by installing a Vigi

b

module (characteristics and selection criteria on next page) directly on the circuit

breaker terminals It directly actuates the trip unit (magnetic, thermal-magnetic or

Micrologic).

Circuit breaker combined with a Vigirex relay

Compact NSX circuit breaker + Vigirex relay

Vigirex relays may be used to add external earth-leakage protection to Compact

NSX circuit breakers. The circuit breakers must be equipped with an MN or MX

voltage release. The Vigirex relays add special tripping thresholds and time delays

for earth-leakage protection.

Vigirex relays are very useful when faced with ma

j

or installation constraints (circuit

breaker already installed and connected, limited space available, etc.).

Vigirex-relay characteristics

Sensitivity ad

j

ustable from 30 mA to 250 mA and 9 time-delay settings (0 to

b

4.5 seconds).

Closed toroids up to 630 A (30 to 300 mm in diameter), split toroids up to 250 A

b

(46 to 110 mm in diameter) or rectangular sensors up to 630 A.

50/60 Hz, 400 Hz distribution systems.

b

Options

Trip indication by a fail-safe contact

b

Pre-alarm contact and LED, etc.

b

Compliance with standards

IEC 60947-2, annex M

b

IEC/EN 60755: general requirements for residual-current operated protective

b

devices

IEC/EN 61000-4-2 to 4-6: immunity tests

b

CISPR11: radio-frequency radiated and conducted emission tests

b

UL1053 and CSA22.2 No. 144 for RH10, RH21 and RH99 relays at supply

b

voltages up to and including 220/240 V.

044322

Earth-leakage relay.

051352

Separate toroids.

PB103579-21

Vigicompact NSX100 to 630.