Oblong fixings :
Attachment at
3 points possible
Note :
40-250 VA transformers have juxtaposed windings with an insulated barrier to provide
insulation and interference filtering. Higher ratings have an electrostatic screen
between windings
n
Dimensions
Fig. 3 : 1 600 to 2 500 VA
Fig. 4 : 4 000 to 8 000 VA
Power
Dimensions
Fixing
1
Weight
Cat. Nos.
Fig.
(mm)
(mm)
(VA)
A
B
C
F
G
Ø
(Kg)
0442 31/61
40
1
94
78
113
50
100
5·2
1·23
0442 32/62
63
1
94
85
113
50
100
5·2
1·56
0442 33/63
100
1
94
94
113
50
100
5·2
1·95
0442 34/64
160
1
94
112
113
50
100
5·2
2·6
0442 35/65
250
1
106
123
115
50
100
5·2
3·82
0442 36/66
400
1
120
140
140
62·5
125
5·2
5·62
0442 37/67
630
2
150
158
206
100
175
7
9·9
0442 38/68
1000
2
150
199
206
100
175
7
14·9
0442 39/69
1600
3
220
245
191
150
153
9
25·6
0442 40/70
2500
3
300
292
171
200
114
9
33·1
0442 71
4000
4
230
340
205
180
130
11
31
A
B
F
G
C
Ø
G
C
Ø
B
F
A
Fig. 2 : 630 to 1 000 VA
Fig. 1 : 40 to 400 VA
F
Ø
A
B
GC
F
GC
A
Ø
B
6
n
Electrical characteristics
n
Fixing
Voltage adjustment
Single phase 50-60 Hz - Class 1
Insulation voltage between windings : 4 510 V
Maximum ambient operating temperatures : 50 °C without derating
No-
On-
Voltage
Connection capacity
Cat. Nos.
Power
Admissible instantaneous power (VA) at cos
ϕ
of :
load
load
drop as (%)
Efficiency (%)
Ucc
Primary
Secondary
(VA)
loss
loss
1
with cos
ϕ
:
with cos
ϕ
:
(%)
cable (mm
2
) cable (mm
2
)
0·2
0·3
0·4
0·5
0·6
0·7
0·8
0·9
1
(W)
(W)
0·3
0·6
1
0·3
0·6
1
flexible rigid flexible rigid
Primary 230-400 V ± 15 V - Secondary 24-48 V
0442 31
40
63
58
55
52
50
48
48
49
60
3·9
7·3
8·7 10·5 8·5
62
77
84 10·0
1 to 4
1 to 4
1 to 4
1 to 4
0442 32
63
110
102
94
87
83
79
77
78
91
6·0
14·2
7·5
9·4 8·5
57
73
82
9·0
1 to 4
1 to 4
1 to 4
1 to 4
0442 33
100
200
180
160
150
140
130
130
130
150
8·2
15·1
7·3
9·3 8·9
66
80
87
8·9
1 to 4
1 to 4
1 to 4
1 to 4
0442 34
160
340
300
270
250
230
220
210
210
230 11·2
24·6
5·8
7·6 7·7
66
80
87
7·2
1 to 4
1 to 4
1 to 4
1 to 4
0442 35
250
550
490
450
420
400
380
370
370
430 14·9
31·4
5·2
6·6 6·2
70
83
89
6·1
1 to 4
1 to 4
1 to 4
1 to 4
0442 36
400 1800 1300 1100
900
800
700
600
600
500 18·3
46·3
2·1
3·7 5·6
72
84
90
4·2
1 to 4
1 to 4
1 to 4
1 to 4
0442 37
630 2700 2200 1900 1700 1500 1300 1200 1200 1200 24·1
49·4
2·0
3·0 3·9
79
88
93
3·3 1 to 16 1 to 16 1 to 16 1 to 16
0442 38
1000 3400 2800 2300 2000 1800 1600 1500 1400 1300 44·2
74·4
1·3
1·9 2·9
80
89
93
2·4 1 to 16 1 to 16 1 to 16 1 to 16
0442 39
1600 12800 10900 9500 8500 7700 7100 6700 6400 6600 65·5
94·7
1·1
1·6 1·9
84
91
94
1·7 2·5 to 10 1·5 to 16 4 to 16 1·5 to 25
0442 40
2500 4300 3900 3600 3300 3100 3000 2900 2900 3400 86·5 143·4
1·8
2·2 2·0
84
91
95
1·9 4 to 16 1·5 to 25 4 to 35 2·5 to 50
Primary 230-400 V ± 15 V - Secondary 115-230 V
0442 61
40
62
57
53
50
48
47
46
47
57
3·9
7·4
8·7 10·5 8·8
62
76
84 10·1
1 to 4
1 to 4
1 to 4
1 to 4
0442 62
63
110
100
93
86
82
78
76
76
90
6·0
11·8
7·6
9·6 8·9
62
76
84
9·2
1 to 4
1 to 4
1 to 4
1 to 4
0442 63
100
200
180
160
150
140
140
130
130
150
8·2
17·3
7·2
9·2 8·6
63
78
85
8·7
1 to 4
1 to 4
1 to 4
1 to 4
0442 64
160
330
300
270
250
240
230
220
220
250 11·2
23·4
5·8
7·4 7·1
67
80
87
6·9
1 to 4
1 to 4
1 to 4
1 to 4
0442 65
250
560
510
460
430
410
390
380
370
430 14·9
31·7
5·2
6·6 6·2
70
83
89
6·1
1 to 4
1 to 4
1 to 4
1 to 4
0442 66
400 2200 1700 1400 1200 1000
910
830
760
730 18·3
43·9
2·1
3·6 5·2
73
85
90
4·1
1 to 4
1 to 4
1 to 4
1 to 4
0442 67
630 2700 2200 1800 1600 1400 1200 1100 1000 1000 24·1
53·2
2·1
3·3 4·5
78
88
92
3·6 1 to 16 1 to 16 1 to 16 1 to 16
0442 68
1000 3400 2800 2300 2000 1800 1600 1500 1400 1300 44·2
73·6
1·3
2·0 2·7
80
89
93
2·2 1 to 16 1 to 16 1 to 16 1 to 16
0442 69
1600 8700 7500 6600 6100 5400 5000 4700 4500 4700 65·5
95·3
1·1
1·5 1·8
83
91
94
1·5 2·5 to 10 1·5 to 16 2·5 to 10 1·5 to 16
0442 70
2500 9200 8300 7600 7100 6700 6300 6200 6100 7100 86·5 150·1
1·8
2·3 2·2
83
91
94
2·0 4 to 16 1·5 to 25 4 to 16 1·5 to 25
0442 71
4000 16500 14300 12700 11400 10500 9800 9200 8900 9500 87·4 234·8
2·1
2·9 3·3
84
91
94
2·7 4 to 16 1·5 to 25 4 to 16 1·5 to 25
U supply (U
1
)
1) if U
1
> 230 or 400 V
2) if I
2
< I
2n
(if the load is less than the nominal load reduce
the secondary voltage)
O
O
O
O
O
+ 15 V
0 V
– 15 V
230 V
400 V
U supply (U
1
)
if U
1
= 230 or 400 V with load I
2
= I
2n
O
O
O
O
O
+ 15 V
0 V
– 15 V
230 V
400 V
if U
1
< 230 or 400 V with load I
2
= I
2n
O
O
O
O
O
+ 15 V
0 V
– 15 V
230 V
400 V
U supply (U
1
)
1 : Up to 250 VA may be fixed to symmetrical
4
DIN rail
1 : Total losses at nominal load
On perforated plates Lina 25 and on Lina 12 . 5 plates
p. 23
On symmetrical rail
4
up to 250 VA
fixing centres pitch 25 mm up to 1000 VA
control, signalling and safety isolation transformers